9.3.2.4

SIMATIC HMI addressing

You can use a SIMATIC HMI as a PROFIBUS master (master class 2) to access SINAMICS
directly. With respect to SIMATIC HMI, SINAMICS behaves like a SIMATIC S7. For
accessing drive parameters, the following simple rule applies:
● Parameter number = data block number
● Parameter sub-index = bit 0 ... 9 of data block offset
● Drive object number = bit 10 ... 15 of data block offset
Pro Tool and WinCC flexible
The SIMATIC HMI can be configured flexibly with "Pro Tool" or "WinCC flexible".
The following specific settings for drives must be observed when configuration is carried out
with Pro Tool or WinCC flexible.
Controllers: Protocol always "SIMATIC S7 - 300/400"
Table 9- 35
Network parameter profile
Network parameter baud rate
Communication partner address
Communication partner
slot/subrack
Table 9- 36
Name
Control
Type
Area
DB
(data block number)
DBB, DBW, DBD
(data block offset)
Length
Acquisition cycle
No. of elements
Decimal places
Function Manual
Function Manual, 01/2011, 6SL3097-4AB10-0BP3
Other parameters
Field
Tags: "General" tab
Field
9.3 Communication via PROFIBUS DP
Value
DP
Any
PROFIBUS address of the drive unit
don't care, 0
Value
Any
Any
Depending on the addressed parameter value,
e.g.:
INT: for integer 16
DINT: for integer 32
WORD: for unsigned 16
REAL: for float
DB
Parameter number
1 ... 65535
Drive object No. and sub-index
bit 15 ... 10: Drive object No. 0 ... 63
bit 9 ... 0: Sub-index 0 ... 1023
or expressed differently
DBW = 1024 * drive object No. + sub-index
Not activated
Any
1
Any
Communication
595