Diagnostics
5.2 Diagnostics via STARTER
Example of a measurement
Assumption:
The actual speed (r0063) is to be output for a drive via measuring socket T1.
How do you do it?
1. Connect and set the measuring device.
2. Interconnect the signal (e.g. STARTER).
3. Parameterize the signal characteristic (scaling, offset, limitation).
Function diagrams (see SINAMICS S110 List Manual)
● 8134 measuring sockets
Overview of important parameters (see SINAMICS S110 List Manual)
Adjustable parameters
● p0771[0...1] CI: Measuring sockets signal source
● p0777[0...1] Measuring sockets characteristic value x1
● P0778[0...1] Measuring sockets characteristic value y1
● p0779[0...1] Measuring sockets characteristic value x2
● p0780[0...1] Measuring sockets characteristic value y2
● p0783[0...1] Measuring sockets offset
● p0784[0...1] Measuring sockets limit on/off
Display parameters
● r0772[0...1] Measuring sockets output signal
● r0774[0...1] Measuring sockets output voltage
● r0786[0...1] Measuring sockets normalization per volt
104
Interconnect the connector input (CI) belonging to the measuring socket with the desired
connector output (CO).
CI: p0771[1] = CO: r0063
Function Manual, 01/2011, 6SL3097-4AB10-0BP3
Function Manual