Siemens Sinamics S110 Function Manual page 41

Hide thumbs Also See for Sinamics S110:
Table of Contents

Advertisement

2. Connecting cable
Cable lengths
Table 2- 2
9.6 k to 187.5 k
500 k
1.5 M
3 to 12 M
Function Manual
Function Manual, 01/2011, 6SL3097-4AB10-0BP3
– CP5511 (PROFIBUS connection via PCMCIA card in the notebook as programming
device)
PROFIBUS card CP5511 permits a maximum of 10 slave connections to be
established. For large projects (many CUs) with several drive units - and therefore
more than 10 PROFIBUS slaves - problems can be encountered when STARTER
goes online with the notebook.
Remedy: Replace interface card CP5511 with a CP5512 interface card or via menu
item "Select target system/target devices..." only select the drive units that you
actually want to work with.
– CP5512 (PROFIBUS connection via CARDBUS)
Configuration: PCMCIA type 2 card + adapter with 9-pin SUB-D socket for connection
to PROFIBUS.
For MS Windows 2000/XP Professional and PCMCIA 32 only
Order No.: 6GK1551-2AA00
– CP5611 A2 (PROFIBUS connection via short PCI card)
Configuration: Short PCI card with 9-pin SUB-D socket for connection to PROFIBUS.
Not for Windows 95/98SE
Order No.: 6GK1561-1AA01
– CP5613 A2 (PROFIBUS connection via short PCI card)
Configuration: Short PCI card with 9-pin SUB-D socket for connection to PROFIBUS.
Order No.: 6GK1561-3AA01
– CP5711 (PROFIBUS connection via USB port (USB V2.0))
Configuration: USB port (USB V2.0) + adapter with 9-pin SUB-D socket connector to
connect to PROFIBUS.
Used with driver SIMATIC Net PC Software Edition 2008 + SP2
Order No.: 6GK1571-1AA00
– between: CP 5xxx ↔ PROFIBUS
Order No.: 6ES7901-4BD00-0XA0
– MPI cable (SIMATIC S7)
Order No.: 6ES7901-0BF00-0AA0
Permissible PROFIBUS cable lengths
Baud rate [bit/s]
Commissioning preparations for PROFIBUS
2.2 PROFIBUS components
Max. cable length [m]
1000
400
200
100
39