M800V/M80V Series PLC Programming Manual (1/2)
7 Basic Instructions
7.3 Output Instructions
SET: Setting devices (ON)
Setting
Bit device
data
X
Y
M
L
F
D
[Instruction symbol] [Execution condition]
SET
 Setting data
Setting data
D
Bit device number to be set (ON)
 Functions
 When SET input is ON, the designated devices respond as follows:
Device
Bit device
Coils and contacts turned ON
Word device
Designation bit set at 1
 Devices turned ON will stay ON even if SET input goes to OFF.
Devices turned ON by the SET instruction can be turned OFF by the RST instruction.
X5
X7
 Device status does not change when SET input is OFF.
 Arithmetic errors
 There are no arithmetic errors associated with the SET instruction.
Usable devices
B SB
T SM V
T
C
SET input
Meaning
Device status
X5
OFF
SET Y10
X7
OFF
RST Y10
Y10 OFF
Con-
Word device
stant
D
R/ZR W SW SD
Z
K
ON
ON
ON
143
Digit
Pointer
designa-
Index
tion
H
P
SET
D
Data type
Bit
IB-1501667-B