M800V/M80V Series PLC Programming Manual (1/2)
7 Basic Instructions
7.2 Connection Instructions
LDP, LDF, ANDP, ANDF, ORP, ORF: Pulse operation start, pulse series connection, pulse parallel con-
nection
Setting
Bit device
data
X
Y
M
L
F
S
○
○
○
○
○
Instruction symbol
Execution condition
LDP
LDF
ANDP
ANDF
ORP
ORF
Setting data
Setting data
S
Devices used as contacts
Functions
LDP,LDF
LDP is the rising edge pulse operation start instruction, and is ON only at the rising edge of the designated bit device (when
it goes from OFF to ON).
If a word device has been designated, it is ON only when the designated bit changes from 0 to 1.
In cases where there is only an LDP instruction, it acts identically to instructions for the creation of a pulse that are executed
during ON ( □ P).
X0
MOV
X0
A ladder using LDP instruction
LDF is the falling edge pulse operation start instruction, and is ON only at the falling edge of the designated bit device
(when it goes from ON to OFF).
If a word device has been designated, it is ON only when the designated bit changes from 1 to 0.
IB-1501667-B
Usable devices
B SB
T SM V
T
C
○
○
○
○
X1/D0.1
X1/D0.1
X3/D0.3
X3/D0.3
Meaning
X0
K0
D0
X0
M0
A ladder not using an LDP instruction
Con-
Word device
stant
D
R/ZR W SW SD
Z
K
○
○
○
○
○
Bit device number / Bit designation of word device
X2/D0.2
X2/D0.2
MOVP K0 D0
PLS M0
128