M800V/M80V Series PLC Programming Manual (1/2)
7 Basic Instructions
7.3 Output Instructions
OUT (T, ST), OUTH (T): 100 ms, 10 ms timer output
Setting
Bit device
data
X
Y
M
L
F
D
Setting
value
[Instruction symbol] [Execution condition]
OUT T □
(100 ms timer)
OUT ST □
(100 ms retentive tim-
er)
OUTH T □
(10 ms timer)
Setting data
Setting data
D
Timer number
Setting value
Setting value of timer
[Remark]
Timer values can be set only as a decimal constant (K).
Hexadecimal constants (H) cannot be used for timer settings.
The retentive timer (ST) cannot be used for the 10 ms timer.
IB-1501667-B
Usable devices
B SB
T SM V
T
C
○
Set value
(Valid from 1 to 32767 of the contents of data register)
Set value (Valid from 1 to 32767 of the contents of data register)
Meaning
Con-
Word device
stant
D
R/ZR W SW SD
Z
K
○
○
○
○
○
○
Set value (Valid from 1 to 32767)
Set value (Valid from 1 to 32767)
Display of 10ms timer output instruction
138
Digit
Pointer
designa-
Index
tion
H
P
K50
T0
D10
T0
H K50
T0
H D10
T0
Data type
Bit
BIN 16 bits