Wiring

4.12 Connecting the digital inputs and outputs

4.12
Connecting the digital inputs and outputs
4.12.1

Interface description - X07/X08/X05

The G115D converter has four digital inputs (DI 0 to DI 3) and two bidirectional digital
inputs/outputs (DIO 24 and DIO 25). Digital inputs DI 0 and DI 1 can be used to connect an
HTL encoder (track A/B). Digital inputs DI 2 and DI 3 can be used for the safety functions.
bidirectional DI/DO can be parameterized as digital inputs or digital outputs with parameter p0728.
Connector variant
M12 A-coding connector, 5-pin, female
Digital inputs (X07, X08) and bidirectional digital inputs/outputs (X05)
X07
X08
X05
Glanded variant
Digital inputs (X07, X08) and bidirectional digital
inputs/outputs (X05)
Cable gland size: M16 * 1.5; Tightening torque: 10 Nm/88.5 lbf.in
76
Pin
Signal
Description
1
1L+
Unswitched 24 V
2
DI1
Digital input 1
3
1M
Unswitched 0 V
4
DI0
Digital input 0
5
FE
Functional earth
Pin
Signal
Description
1
1L+
Unswitched 24 V
2
DI3
Digital input 3
3
1M
Unswitched 0 V
4
DI2
Digital input 2
5
FE
Functional earth
Pin
Signal
Description
1
2L+
Switched 24 V
2
DIO25
Bidirectional digital output/input 25
3
2M
Switched 0 V
4
DIO24
Bidirectional digital output/input 24
5
FE
Functional earth
Signal
1L+
X07
DI0
DI1
1M
FE
1L+
X08
DI2
DI3
1M
FE
2L+
X05
DIO24
DIO25
2M
FE
Operating Instructions, 12/2020, FW V4.7 SP13, A5E48681219B-002
Description
Unswitched 24 V
Digital input 0
Digital input 1
Unswitched 0 V
Functional earth
Unswitched 24 V
Digital input 2
Digital input 3
Unswitched 0 V
Functional earth
Switched 24 V
Bidirectional digital output/input 24
Bidirectional digital output/input 25
Switched 0 V
Functional earth
SINAMICS G115D distributed drive