• The communication check time by query communication includes a no-data time (3.5 bytes).
This no-data time differs according to the communication speed, so take this no-data time into consideration when setting
the communication check time.
Example: RS-485 terminal communication, Pr. 539 = "0.1 to 999.8 s"
Query communication
Operation mode
PLC (master)
Inverter (slave)
Inverter (slave)
PLC (master)
Pr.539
Communication
check counter
ALM
Broadcast communication
Operation mode
PLC (master)
Inverter (slave)
Inverter (slave)
PLC (master)
Pr.539
Communication
check counter
ALM
NOTE
• For the RS-485 terminal communication, the operation at a communication error occurrence depends on the Pr.502 Stop
mode selection at communication error setting. (Refer to
5.15.7 CC-Link IE Field Network function setting (FRA800-
GF)
Use the following parameters to perform required settings for CC-Link IE Field Network communication between the inverter
and other stations.
• For the details of the CC-Link IE Field Network, refer to
• For the inverter operation at communication error, refer to
• Set the parameters other than Pr.434, Pr.435, and Pr.541 in the same way as when a communication option is used.
Pr.
Name
434
Network number (CC-
N110
Link IE)
435
Station number (CC-Link
N111
IE)
541
Frequency command
N100
sign selection
External
NET
Query Message1
Data absence time
(3.5 bytes or more)
Response Message1
Check start
External
NET
Query Message1
Query Message2
Data absence time
(3.5 bytes or more)
Check start
OFF
page
page
Initial
Setting range
value
0
0 to 255
Enter the network number of the inverter.
0
0 to 255
Enter the station number of the inverter.
0
Signed frequency command value
0
1
Unsigned frequency command value
Query Message2
Response Message2
OFF
Fault
(E.SER)
Time
ON
page
630.)
716.
630.
Description
5.15 (N) Communication operation parameters
1
2
3
4
Fault
(E.SER)
5
Time
ON
6
7
8
9
10
665
5. PARAMETERS