Wiring Of Control Circuit - Mitsubishi Electric FR-A820-00046 (0.4K) Instruction Manual

Fr-a800 series
Hide thumbs Also See for FR-A820-00046 (0.4K):
Table of Contents

Advertisement

• When using an external power supply for transistor output
Sink logic
Use terminal PC as a common terminal, and perform wiring as
follows. (Do not connect terminal SD on the inverter with the
terminal of 0 V for the external power supply. When using
terminals PC-SD as a 24 VDC power supply, do not install an
external power supply in parallel with the inverter. Doing so
may cause a malfunction in the inverter due to undesirable
currents.)
QY40P type transistor
output unit
TB1
TB2
TB17
Constant
voltage
circuit
TB18
24 VDC SD
2.6.3

Wiring of control circuit

 Control circuit terminal layout
• Recommended cable gauge: 0.3 to 0.75 mm
AM
5 10E 10 SE SE
*1
This terminal operates as terminal FM for the type FM inverter. For the type CA inverter, the terminal operates as terminal CA.
 Wiring method
 Power supply connection
For the control circuit wiring, strip off the sheath of a cable, and use it with a blade terminal. For a single wire, strip off the sheath
of the wire and apply directly.
Insert the blade terminal or the single wire into a socket of the terminal.
1.
Strip off the sheath for the below length. If the length of the sheath peeled is too long, a short circuit may occur with
neighboring wires. If the length is too short, wires might come off.
Wire the stripped cable after twisting it to prevent it from becoming loose. In addition, do not solder it.
Cable sheath stripping length
Inverter
STF
24 VDC
(SD)
STR
PC
Current flow
2
∗1
2
5
4
1 F/C +24 SD
So SOC
RUN
SU
IPF OL FU
10 mm
Source logic
Use terminal SD as a common terminal, and perform wiring as
follows. (Do not connect terminal PC on the inverter with the
terminal of +24 V for the external power supply. When using
terminals PC-SD as a 24 VDC power supply, do not install an
external power supply in parallel with the inverter. Doing so
may cause a malfunction in the inverter due to undesirable
currents.)
QY80 type transistor
output unit
Constant
voltage
Fuse
circuit
Current flow
SD
SIC
S1 S2 PC
A1
B1
PC RL RM RH RT AU
STP MRS RES
Inverter
PC
TB1
STF
24 VDC
(SD)
TB2
STR
TB17
TB18
SD
C1
A2
B2
C2
SD SD
STF STR JOG
CS
2. INSTALLATION AND WIRING
2.6 Control circuit
1
2
3
4
5
6
7
8
9
10
73

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fr-a820-00167 (2.2k)Fr-a820-00046-gf (0.4k)Fr-a820-00250 (3.7k)Fr-a820-00105-gf (1.5k)Fr-a820-00077 (0.75k)Fr-a820-00250-gf (3.7k) ... Show all

Table of Contents