Mitsubishi Electric FR-A820-00046 (0.4K) Instruction Manual page 433

Fr-a800 series
Hide thumbs Also See for FR-A820-00046 (0.4K):
Table of Contents

Advertisement

• On the I/O terminal monitor, the upper LEDs indicate the input terminal status, and the lower LEDs indicate the output
terminal status.
STP (STOP)
AU
RM
RH
RT
RL
RUN
OL
ABC1
SU
ABC2
IPF
• The decimal point of the first digit on the LED is lit for the input option terminal monitor.
X1
X4
X2
X5
X6
X0
X3
X12
X15
X10 X11
X13 X14
DY
• The decimal point of the second digit on the LED is lit for the output option terminal monitor.
Y1
Y2
Y4
Y5
Y6
Y3
Y0
RA3
RA1 RA2
 Cumulative energy monitoring and resetting (Pr.170, Pr.891)
• During the monitoring of cumulative energy (Pr.52 = "25"), the monitored output power is added up. Its readout is refreshed
every 100 ms. (The values are saved in EEPROM every hour.)
• Increments and ranges of monitoring on the operation panel or parameter unit and via communication (RS-485
communication or other communication with communication option installed) are as follows.
On operation panel or parameter unit
Range
0 to 999.99 kWh
1000.0 to 9999.9 kWh
10000 to 99999 kWh
*1
Energy is measured in the range of 0 to 99999.99 kWh, and displayed in five digits. The cumulative energy up to 999.99 kWh is displayed in 0.01
increments such as "999.99", and that of 1000 kWh or more is displayed in 0.1 increments such as "1000.0".
• The digit of monitored value can be moved to the right by the number of Pr.891 Cumulative power monitor digit shifted
times. For example, when the cumulative energy is 1278.56 kWh and Pr.891 is set to "2", "12.78" is displayed (in 100's of
units) on the operation panel and the communication data is converted into "12".
• When Pr.891 = "0 to 4" and the cumulative energy reaches more than the upper limit of readout, the readout peaks out at
the upper limit, which indicates that moving digit is necessary. When Pr.891 = "9999" and the cumulative energy reaches
more than the upper limit of readout, cumulative value is reset to 0 and the metering restarts.
• Setting "0" in Pr.170 clears the cumulative energy value.
NOTE
• Once "0" is set in Pr.170, the setting of Pr.170 is turned to "9999" or "10" afterwards.
432
5. PARAMETERS
5.11 (M) Item and output signal for monitoring
RES
JOG
STF
CS
STR
MRS
FU
So (SO)
X7
X8
X9
Decimal point LED of second digit LED is always ON
*1
Increment
Pr.170 = 10
0.01 kWh
0.1 kWh
0 to 9999 kWh
1 kWh
Input terminal
Center line is always ON
Output terminal
Center line is always ON
Decimal point LED of first digit LED is always ON
FR-A8AY
Center line is always ON
FR-A8AR
Via communication
Range
Pr.170 = 9999
0 to 65535 kWh
(initial value)
- Display example -
When signals STF,
RH and RUN are on
A
Increment
1 kWh

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fr-a820-00167 (2.2k)Fr-a820-00046-gf (0.4k)Fr-a820-00250 (3.7k)Fr-a820-00105-gf (1.5k)Fr-a820-00077 (0.75k)Fr-a820-00250-gf (3.7k) ... Show all