• 400 V class (440 V input power supply, with a power factor improving AC or DC reactor)
Applicable
Terminal
Tightening
inverter model
screw
torque
*4
FR-A840-[]
size
00023(0.4K)
M4
1.5
00038(0.75K)
M4
1.5
00052(1.5K)
M4
1.5
00083(2.2K)
M4
1.5
00126(3.7K)
M4
1.5
00170(5.5K)
M4
1.5
00250(7.5K)
M4
1.5
00310(11K)
M5
2.5
00380(15K)
M5
2.5
00470(18.5K)
M6
4.4
00620(22K)
M6
4.4
00770(30K)
M6
4.4
00930(37K)
M8
7.8
01160(45K)
M8
7.8
01800(55K)
M8
7.8
02160(75K)
M10
14.7
02600(90K)
M10
14.7
03250(110K)
M10(M12)
14.7
03610(132K)
M10(M12)
14.7
04320(160K)
M12 (M10) 24.5
04810(185K)
M12 (M10) 24.5
05470(220K)
M12 (M10) 46
06100(250K)
M12 (M10) 46
06830(280K)
M12 (M10) 46
*1
For the FR-A820-03160(55K) or lower and FR-A840-01800(55K) or lower, it is the gauge of a cable with the continuous maximum permissible
temperature of 75°C (HIV cable (600 V grade heat-resistant PVC insulated wire), etc.). It assumes a surrounding air temperature of 50°C or lower
and the wiring distance of 20 m or shorter.
For the FR-A820-03800(75K) or higher, FR-A840-02160(75K) or higher, it is the gauge of the cable with the continuous maximum permissible
temperature of 90°C or higher. It assumes a surrounding air temperature of 50°C or lower and in-enclosure wiring.
*2
For all the 200 V class capacities and FR-A840-01160(45K) or lower, it is the gauge of a cable with the continuous maximum permissible
temperature of 75°C (THHW cable). It assumes a surrounding air temperature of 40°C or lower and the wiring distance of 20 m or shorter.
For the FR-A840-01800(55K) or higher, it is the gauge of a cable with the continuous maximum permissible temperature of 90°C (THHN cable).
It assumes a surrounding air temperature of 40°C or lower and in-enclosure wiring.
(For the use in the United States or Canada, refer to "Instructions for UL and cUL" in the Instruction Manual (Startup) or Instruction Manual
(Hardware).)
*3
For the FR-A820-00770(15K) or lower and the FR-A840-01160(45K) or lower, it is the gauge of a cable with the continuous maximum permissible
temperature of 70°C (PVC cable). It assumes a surrounding air temperature of 40°C or lower and the wiring distance of 20 m or shorter.
For the FR-A820-00930(18.5K) or higher and the FR-A840-01800(55K) or higher, it is the gauge of a cable with the continuous maximum
permissible temperature of 90°C (XLPE cable). It assumes a surrounding air temperature of 40°C or lower and in-enclosure wiring.
(Selection example mainly for use in Europe.)
*4
The terminal screw size indicates the size of a terminal screw for R/L1, S/L2, T/L3, U, V, W, PR, PX, P/+, N/-, P1, and a screw for earthing
(grounding).
The screw size for terminals PR and PX on FR-A820-00340(5.5K) and FR-A820-00490(7.5K) is indicated in parentheses.
The screw size for earthing (grounding) terminal on FR-A820-00930(18.5K) or higher and FR-A840-04320(160K) or higher is indicated in
parentheses.
The screw size for terminal P/+ for option connection on the FR-A840-03250(110K) and FR-A840-03610(132K) is indicated in parentheses.
The line voltage drop can be calculated by the following formula:
× wire resistance [mΩ/m] × wiring distance [m] × current [A]
Line voltage drop [V] =
Use a larger diameter cable when the wiring distance is long or when it is desired to decrease the voltage drop (torque
reduction) in the low speed range.
NOTE
• Tighten the terminal screw to the specified torque.
A screw that has been tightened too loosely can cause a short circuit or malfunction.
A screw that has been tightened too tightly can cause a short circuit or malfunction due to the unit breakage.
Crimp terminal
HIV cables, etc. (mm
R/L1,
R/L1,
N·m
S/L2,
U, V, W
S/L2,
T/L3
T/L3
2-4
2-4
2
2-4
2-4
2
2-4
2-4
2
2-4
2-4
2
2-4
2-4
2
2-4
2-4
2
2-4
2-4
2
5.5-6
5.5-6
3.5
5.5-5
5.5-5
5.5
5.5-6
5.5-6
5.5
8-6
8-6
8
14-6
14-6
14
22-8
22-8
22
22-8
22-8
22
38-8
38-8
38
60-10
60-10
60
60-10
60-10
60
60-10
60-10
60
80-10
80-10
80
100-12 100-12 100
150-12 150-12 125
150-12 150-12 150
100-12 100-12 2×100 2×100 2×100 60
100-12 100-12 2×100 2×100 2×125 60
1000
Cable gauge
2
*1
)
AWG/MCM
Earthing
R/L1,
U, V,
P/+,
(grounding)
S/L2,
W
P1
cable
T/L3
2
2
2
14
2
2
2
14
2
2
2
14
2
2
2
14
2
2
2
14
2
2
2
14
2
3.5
3.5
12
3.5
3.5
3.5
12
5.5
5.5
5.5
10
5.5
8
5.5
10
8
14
8
8
14
22
14
6
22
22
14
4
22
22
14
4
38
38
22
2
60
60
22
1/0
60
60
22
1/0
60
80
22
3/0
80
80
38
3/0
100
100
38
4/0
125
150
38
250
150
150
38
300
2×4/0 2×4/0 2×95
2×4/0 2×4/0 2×95
*2
2
PVC cables, etc. (mm
R/L1,
Earthing
U, V,
U, V,
S/L2,
(grounding)
W
W
T/L3
cable
14
2.5
2.5
2.5
14
2.5
2.5
2.5
14
2.5
2.5
2.5
14
2.5
2.5
2.5
14
2.5
2.5
2.5
14
2.5
2.5
2.5
14
2.5
2.5
2.5
12
4
4
4
10
6
6
6
10
6
6
6
8
10
10
10
6
16
16
16
4
25
25
16
4
25
25
16
2
50
50
25
1/0
50
50
25
1/0
50
50
25
3/0
50
50
25
3/0
70
70
35
4/0
95
95
50
250
120
120
70
300
150
150
95
2×95
95
2×95
95
2. INSTALLATION AND WIRING
2.5 Main circuit terminals
1
*3
)
2
3
4
5
6
7
8
9
10
65

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fr-a820-00167 (2.2k)Fr-a820-00046-gf (0.4k)Fr-a820-00250 (3.7k)Fr-a820-00105-gf (1.5k)Fr-a820-00077 (0.75k)Fr-a820-00250-gf (3.7k) ... Show all

Table of Contents