2.5.6

CC-Link IE Field Network Basic

The CC-Link IE Field Network Basic enables CC-Link IE communication using the general-purpose Ethernet-based
technology. The CC-Link IE Field Network Basic is suited to small-scale equipment for which high-speed control is not
necessary, and can coexist with the standard Ethernet TCP/IP (HTTP, FTP, etc.).
Pr.
Name
541
Frequency command
N100
sign selection
544
CC-Link extended setting
N103

804
Torque command source
D400
selection

810
Torque limit input
H700
method selection


The setting is applied after an inverter reset or power-ON.

The setting is available for the FR-A800-E only.
Communication specifications
Item
Transmission speed
Communication method
Connectable units
Topology
Number of occupied stations
Maximum number of links per
station
Reference response time


The reference response time is the period from when the inverter receives a command from the master until the inverter returns the response to
the master.
Initial setting
• To select the CC-Link IE Field Network Basic for the application, set "61450" in any of Pr.1427 to Pr.1429 Ethernet
function selection 1 to 3. (Refer to
• To limit the network devices that send the command through the Ethernet network (CC-Link IE Field Network Basic), set the
range of IP addresses (Pr.1449 to Pr.1454). (Refer to
• Use Pr.1432 Ethernet communication check time interval to set the interval of the check time (for signal loss detection)
for all devices with IP addresses in the range specified for Ethernet command source selection (Pr.1449 to Pr.1454). (Refer
to
page
25.)
NOTE
• To use the CC-Link IE Field Network Basic, do not install the FR-A8NC to the inverter. (Doing so disables communication
through the CC-Link IE Field Network Basic.)
• When the CC-Link IE Field Network Basic is used, a communication error (E.EHR) occurs regardless of the Pr.1432
Ethernet communication check time interval setting in the following cases: the data addressed to the own station is not
received for the predetermined timeout period or longer, or the status bit of the cyclic transmission addressed to the own
station turns OFF (when the master gives a command to stop the cyclic transmission). (For the details of the timeout period,
status bit of the cyclic transmission, and command to stop the cyclic transmission, refer to the Instruction Manual of the
master controller which supports the CC-Link IE Field Network Basic.)
Initial
Setting range
value
0
0
1
0, 1, 12, 14, 18, 24,
0
28, 100, 112, 114,
118, 128
0
0 to 6
0
0 to 2
Description
100 Mbps
UDP/IP
Master: 1
Slave: up to 64
Star
Occupies one station
RX
64 (8 bytes)
RY
64 (8 bytes)
RWr
32 (64 bytes)
RWw
32 (64 bytes)
Within 15 ms
page
21.)
page
(N) Operation via communication and its settings
Frequency command without sign
Frequency command with sign
The function of the remote registers can be extended
when the CC-Link IE Field Network Basic is used.
In the torque control mode, the torque command source
can be selected.
The torque limit input method can be selected.
24.)
Description
PARAMETER
2
GROUP
N
51