5.8.7
Lift operation (automatic acceleration/
deceleration)
V/F
V/F
V/F
The inverter can be operated according to the load pattern of the lift with counterweight.
Pr.
Name
292
Automatic acceleration/
F500
deceleration
61
Reference current
F510
64
Starting frequency for
F520
elevator mode
*1
The setting range of FR-A820-03160(55K) or lower and FR-A840-01800(55K) or lower
*2
The setting range of FR-A820-03800(75K) or higher and FR-A840-02160(75K) or higher
 Lift operation (Pr.292 = "5, 6")
• When Pr.292 Automatic acceleration/deceleration is set to "5" or "6", the lift operation is selected, and each setting is
changed, as shown in the following table.
• During power driving, sufficient torque is generated, and during regenerative driving and during driving with no load, the
torque boost setting is adjusted automatically so as not to activate the overcurrent protective function by overexcitation.
Name
Torque boost
Starting frequency
Base frequency voltage
Stall prevention operation level Pr.22 (150%), etc.
When Pr.0 =6%
Torque boost (%)
Pr.0
Torque boost 0%
Regenerative
current
• If the lift has a load in which the rated current of the inverter is exceeded, the maximum torque may be insufficient.
For a lift without counterweight, setting Pr.14 Load pattern selection to "2 or 3" (for lift load) and setting Pr.19 Base
frequency voltage appropriately give the maximum torque a greater advantage than when selecting the lift operation.
368
5. PARAMETERS
5.8 (F) Setting of acceleration/deceleration time and acceleration/deceleration pattern
Initial
value
0
1
11
0
3
5
6
7, 8
0 to 500 A
9999
0 to 3600 A
9999
0 to 10 Hz
9999
9999
Normal operation
Pr.0 (6/4/3/2/1%)
Pr.13 (0.5 Hz)
Pr.19 (9999)
Pr.292 = "5"
Pr.292 = "6"
6%
3%
0
100
120 140
115
Setting range
Normal operation
Shortest acceleration/deceleration
(without brakes)
Shortest acceleration/deceleration
(with brakes)
Optimum acceleration/deceleration
Lift operation 1 (stall prevention operation level 150%)
Lift operation 2 (stall prevention operation level 180%)
Brake sequence 1, 2 (Refer to
*1
Set the reference current during shortest (optimum)
acceleration/deceleration.
*2
Rated output current value reference of the inverter
Set the starting frequency for the lift operation.
Starting frequency is 2 Hz.
Multi-rating
(Pr.570)
Changes according to the output
current (as shown below)
Pr.64 (2 Hz) Accelerate after 100 ms
hold.
220 V class (440 V class)
0( SLD)
110%
1 (LD)
120%
2 (ND)
150%
Initial value
3 (HD)
200%
Driving
current
(%)
Description
(Refer to
365.)
page
541.)
Lift operation (Pr.292)
5
6
115%
140%
180%
230%
page