• Use Pr.428 Command pulse selection to select a type of pulse train input to the FR-A8AL.
Pr.428 setting
0 (initial value)
Negative
1
logic
2
3
Positive
4
logic
5
• Use Pr.432 Pulse train torque command bias and Pr.433 Pulse train torque command gain to set the bias and gain
values for the torque command respectively.
NOTE
• For the details of the FR-A8AL, refer to the Instruction Manual of the FR-A8AL.
 Torque command given through the CC-Link / CC-Link IE Field Network /
PROFIBUS-DP (Pr.804 = "3, 5, 6")
• Set the torque command value via the CC-Link communication (FR-A8NC/PLC function), CC-Link IE Field Network
communication (FR-A8NCE/FR-A800-GF), or PROFIBUS-DP communication (FR-A8NP).
• For speed limit when "3 or 5" is set in Pr.804 via the CC-Link communication, Pr.807 Speed limit selection becomes
invalid and Pr.808 Forward rotation speed limit/speed limit and Pr.809 Reverse rotation speed limit/reverse-side
speed limit become valid for speed limit. (When Pr.544 CC-Link extended setting = "0, 1, 12, 100, or 112")
• For the CC-Link communication, Pr.807 is valid when the extended cyclic setting of CC-Link communication is quadruple
or octuple. For CC-Link IE Field Network, Pr.807 is always valid.
Pr.804
setting
CC-Link/PLC function
Torque command by
1
Pr.805, Pr.806
Torque command by
remote register (RWw1
3
*2
or RWwC)
Torque command by
remote register (RWw1
5
*2
or RWwC)
Torque command by
6
Pr.805, Pr.806
*1
The torque command can also be given from operation panel or parameter unit.
272
5. PARAMETERS
5.4 Torque control under Real sensorless vector control and Vector control
Command pulse train type
Forward pulse train
Reverse pulse train
Pulse train + sign
A phase pulse train
B phase pulse train
Forward pulse train
Reverse pulse train
Pulse train + sign
A phase pulse train
B phase pulse train
Torque command value
Pr.433
setting
Pr.432
setting
Torque command input
CC-Link IE
*1
Torque command by
remote register
*2
(RWw2)
Torque command by
remote register
*2
(RWw2)
*1
During forward rotation During reverse rotation
PP
NP
PP
L
NP
PP
NP
PP
NP
PP
NP
H
PP
NP
Pulse train input frequency
0
400kpps
PROFIBUS-DP
Torque command by
*1
Pr.805, Pr.806
600 to 1400
Torque command by the
(-400% to 400%)
buffer memory of
PROFIBUS-DP (REF1 to
*2
7)
Torque command by the
buffer memory of
PROFIBUS-DP (REF1 to
-32768 to 32767 (complement of 2)
*2
7)
(-327.68% to 327.67%)
Torque command by
*1
Pr.805, Pr.806
H
L
Setting
Setting range
increments
1%
0.01%
*3
*3