Mitsubishi Electric FR-A820-00046 (0.4K) Instruction Manual page 518

Fr-a800 series
Hide thumbs Also See for FR-A820-00046 (0.4K):
Table of Contents

Advertisement

NOTE
• If "9999" is set, tuning data will be invalid and the constant values for Mitsubishi Electric motors (SF-PR, SF-JR, SF-HR, SF-
JRCA, SF-HRCA and SF-V5RU (1500 r/min series) and so on) are used.
 Changing the motor constants (when setting motor constants in the
internal data of the inverter)
• Set Pr.71 as follows.
Mitsubishi Electric standard motor
Mitsubishi Electric high-efficiency motor
Mitsubishi Electric constant-torque motor
Mitsubishi Electric high-performance
energy-saving motor
Vector control dedicated motor
Other manufacturer's standard motor
Other manufacturer's constant-torque
motor
• Set desired values as the motor constant parameters. The display units of the read motor constants can be changed with
Pr.684 Tuning data unit switchover. Setting Pr.684 = "1" disables parameter setting changes.
First motor
Second
Pr.
motor Pr.
Motor excitation
82
455
current
90
458
Motor constant (R1)
91
459
Motor constant (R2)
Motor constant (L1)/
92
460
d-axis inductance
(Ld)
Motor constant (L2)/
93
461
q-axis inductance
(Lq)
94
462
Motor constant (X)
Torque current/
859
860
Rated PM motor
current
Frequency search
298
560
gain
*1
For the FR-A820-03160(55K) or lower and FR-A840-01800(55K) or lower.
*2
For the FR-A820-75K(03800) or higher and FR-A840-75K(02160) or higher.
NOTE
• As the motor constants measured in the offline auto tuning have been converted into internal data (****), refer to the following
setting example when making setting. (The value displayed has been converted into a value for internal use. Therefore, simple
addition of a value to the displayed value does not bring the desired effect.)
Setting example: To slightly increase the Pr.90 value (5%)
When "2516" is displayed for Pr.90, set 2642 (2516 × 1.05 = 2641.8) in Pr.90.
Motor
SF-JR, SF-TH
SF-JR 4P 1.5 kW or lower
SF-HR
Others
SF-JRCA 4P and
SF-TH (constant-torque)
SF-HRCA
Others (SF-JRC, etc.)
SF-PR
SF-V5RU (1500 r/min series)
SF-THY
SF-V5RU (other than the 1500 r/min series) 13 (14)
Pr.684 = 0 (initial value)
Name
Setting range
0 to ***, 9999
0 to 32767, 9999
3 (4)
23 (24)
43 (44)
3 (4)
13 (14)
53 (54)
13 (14)
73 (74)
33 (34)
3 (4)
13 (14)
Pr.684 = 1
Setting
Range indication
increments
0 to 500 A, 9999
0 to 3600 A, 9999
*1
0 to 50 Ω, 9999
0 to 400 mΩ, 9999
*1
0 to 50 Ω, 9999
0 to 400 mΩ, 9999
0 to 6000 mH, 9999
1
0 to 400 mH, 9999
0 to 6000 mH, 9999
0 to 400 mH, 9999
0 to 100%, 9999
0 to 500 A, 9999
0 to 3600 A, 9999
1
0 to 32767, 9999
5.13 (C) Motor constant parameters
Pr.71 setting
Initial
Unit
value
indication
*1
*1
0.01 A
*2
*2
0.1 A
*1
0.001 Ω
*2
*2
0.01 mΩ
*1
0.001 Ω
*2
*2
0.01 mΩ
*1
*1
0.1 mH
*2
*2
0.01 mH
9999
*1
*1
0.1 mH
*2
*2
0.01 mH
*1
0.1%
*2
0.01%
*1
*1
0.01 A
*2
*2
0.1 A
1
5. PARAMETERS
1
2
3
4
5
6
7
8
9
10
517

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for: