Mitsubishi Electric FR-A820-00046 (0.4K) Instruction Manual page 469

Fr-a800 series
Hide thumbs Also See for FR-A820-00046 (0.4K):
Table of Contents

Advertisement

Pr.
Name
655
Analog remote output
M530
selection
656
Analog remote output 1 1000%
M531
657
Analog remote output 2 1000%
M532
658
Analog remote output 3 1000%
M533
659
Analog remote output 4 1000%
M534
 Analog remote output (Pr.656 to Pr.659)
• The analog signal of the value set in Pr.656 to Pr.659 (Analog remote output) can be output via terminal FM or CA,
terminal AM and the analog output terminal on the option FR-A8AY.
• When Pr.54 FM/CA terminal function selection = "87, 88, 89, or 90" (Remote output value), the type FM inverter can
output a pulse train via terminal FM.
• For FM output (when Pr.291 Pulse train I/O selection = "0 (initial value) or 1"):
Terminal FM output [pulses/s] = 1440 [Hz] × (Analog remote output value - 1000)/100
Where the output range is 0 to 2400 pulses/s.
• For high-speed pulse output (when Pr.291 Pulse train I/O selection = "10, 11, 20, or 21"):
Terminal FM output [pulses/s] = 50k [Hz] × (Analog remote output value - 1000)/100
Where the output range is 0 to 55k pulses/s.
Pulse speed
800
Terminal FM (FM output)
• When Pr.54 FM/CA terminal function selection = "87, 88, 89, or 90" (remote output), the type CA inverter can output
any analog current via terminal CA.
• Terminal CA output [mA] = 20 [mA] × (Analog remote output value - 1000)/100
Where the output range is 0 to 20 mA.
Output current [mA]
800
468
5. PARAMETERS
5.11 (M) Item and output signal for monitoring
Initial
Setting
value
range
0
1
0
10
11
800 to
1200%
800 to
1200%
800 to
1200%
800 to
1200%
[pulse/s]
2400
1440
0
1000
1100
Analog remote output value [%]
20
0
1000
1100
Analog remote output value [%]
Terminal CA
Remote output data is cleared when the
inverter power is turned OFF.
Remote output data is retained even after
the inverter power is turned OFF.
Remote output data is cleared when the
inverter power is turned OFF.
Remote output data is retained even after
the inverter power is turned OFF.
Value output via the terminal for which "87"
is set in the terminal function selection
parameter (Pr.54 or Pr.158)
Value output via the terminal for which "88"
is set in the terminal function selection
parameter (Pr.54 or Pr.158)
Value output via the terminal for which "89"
is set in the terminal function selection
parameter (Pr.54 or Pr.158)
Value output via the terminal for which "90"
is set in the terminal function selection
parameter (Pr.54 or Pr.158)
Pulse speed
800
1200
Terminal FM (High-speed pulse train output)
1200
Description
Remote output data is cleared
during an inverter reset.
Remote output data is
retained during an inverter
reset.
Set the analog value outputted
via terminal FM or CA, via
terminal AM, and via the
analog output terminal on the
option FR-A8AY.
[pulse/s]
55K
50K
0
1000
1100
Analog remote output value [%]
1200

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fr-a820-00167 (2.2k)Fr-a820-00046-gf (0.4k)Fr-a820-00250 (3.7k)Fr-a820-00105-gf (1.5k)Fr-a820-00077 (0.75k)Fr-a820-00250-gf (3.7k) ... Show all

Table of Contents