INVERTER
FR-A800 Plus
INSTALLATION GUIDELINE
Roll to Roll Function
FR-A820-00046(0.4K) to 04750(90K)(-E)-R2R
FR-A840-00023(0.4K) to 06830(280K)(-E)-R2R
FR-A842-07700(315K) to 12120(500K)(-E)-R2R
A
Thank you for choosing this Mitsubishi Electric Inverter.
This Installation guideline and the enclosed CD-ROM give handling information and precautions for use of this
product.
Do not use this product until you have a full knowledge of the equipment, the safety information and the
instructions.
Please forward this Installation guideline and the CD-ROM to the end user.
1
INSTALLATION AND INSTRUCTIONS ................................................................................ 1
2
WIRING................................................................................................................................ 5
3
FAILSAFE OF THE SYSTEM WHICH USES THE INVERTER............................................... 24
4
PRECAUTIONS FOR USE OF THE INVERTER.................................................................... 25
5
BASIC OPERATION ........................................................................................................... 27
6
TROUBLESHOOTING ........................................................................................................ 45
7
SPECIFICATIONS .............................................................................................................. 48
Art. No. 473174
12082019
Version check
Version B
CONTENTS
800

Advertisement

loading

Summary of Contents for Mitsubishi Electric FR-A800 Plus Series

  • Page 1: Table Of Contents

    FR-A820-00046(0.4K) to 04750(90K)(-E)-R2R FR-A840-00023(0.4K) to 06830(280K)(-E)-R2R FR-A842-07700(315K) to 12120(500K)(-E)-R2R Thank you for choosing this Mitsubishi Electric Inverter. This Installation guideline and the enclosed CD-ROM give handling information and precautions for use of this product. Do not use this product until you have a full knowledge of the equipment, the safety information and the instructions.
  • Page 2 General corrections according “INSTRUCTION MANUAL (STARTUP) – B-0600605-D” For Maximum Safety O Mitsubishi Electric transistorized inverters are not designed or manufactured to be used in equipment or systems in situations that can affect or endanger human life. O When considering this product for operation in special applications such as machinery or systems used in passenger transportation, medical, aerospace, atomic power, electric power, or submarine repeating applications, please contact your nearest Mitsubishi Electric sales representative.
  • Page 3 O A person who took a proper engineering training. Please note if you can take a proper engineering training at your local Mitsubishi Electric office. Such training may be available at your local Mitsubishi Electric office. Contact your local sales office for schedules and locations.
  • Page 4 2.9 m/s² or less for the FR-A840-04320(160K)-R2R or higher. O If halogen-based materials (fluorine, chlorine, bromine, iodine, etc.) infiltrate into a Mitsubishi Electric product, the product will be damaged. Halogen-based materials are often included in fumigant, which is used to sterilize or disinfect wooden packages. When packaging, prevent residual fumigant components from being infiltrated into Mitsubishi Electric products, or use an alternative sterilization or disinfection method (heat disinfection, etc.) for packaging.
  • Page 5 Test operation and adjustment CAUTION O Before starting operation, confirm and adjust the parameters. A failure to do so may cause some machines to make unexpected motions. Operation WARNING O When you have chosen the retry function, stay away from the equipment as it will restart suddenly after an alarm stop. O Since pressing the key may not stop output depending on the function setting status, provide a circuit and switch separately to make an emergency stop (power off, mechanical brake operation for emergency stop, etc).
  • Page 6 Emergency stop CAUTION O Provide a safety backup such as an emergency brake which will prevent the machine and equipment from hazardous conditions if the inverter fails. O When the breaker on the inverter primary side trips, check for the wiring fault (short circuit), damage to internal parts of the inverter, etc. Identify the cause of the trip, then remove the cause and power on the breaker.
  • Page 7: Installation And Instructions

    1 INSTALLATION AND INSTRUCTIONS 1.1 Inverter Type Communica- Symbol Circuit board Plated Symbol Voltage class Symbol Structure, functionality Description Symbol Type Capacity tion type coating conductor 00023 to Inverter SLD rated 200 V class Standard model Without Without Without 12120 current [A] RS-485 0.4 to 500K Inverter ND rated...
  • Page 8 INSTALLATION AND INSTRUCTIONS 1.2 Installation of the inverter O Install the inverter on a strong surface securely with screws. Fix six positions for the FR-A840-04320(160K)-R2R or higher and for the FR-A842-R2R models (separated converter type). O Leave enough clearances and take cooling measures. O Avoid places where the inverter is subjected to direct sunlight, high temperature and high humidity.
  • Page 9 INSTALLATION AND INSTRUCTIONS 1.3 Environment Before installation, check that the environment meets following specifications: Enclosure x = Measurement position LD, SND, ND (initial setting), HD: –10 °C to +50 °C Surrounding air (non-freezing) 5 cm 5 cm *4, *5 temperature SLD: –10 °C to +40 °C (non-freezing) 5 cm With circuit board coating (conforming to IEC 60721-3-3 3C2/3S2):...
  • Page 10 INSTALLATION AND INSTRUCTIONS 1.5 Installing a communication option (FR-A800-E-R2R) To use a communication option, the enclosed earthing (grounding) cable needs to be installed. Install the cable according to the following procedure: a Insert spacers into the mounting holes that will not be tightened with the option mounting screws. b Fit the connector of the communication option to the guide of the connector of the inverter, and insert the option as far as it goes.
  • Page 11: Wiring

    2 WIRING 2.1 Terminal connection diagrams 2.1.1 FR-A820/A840(-E)-R2R  CA type FR-A820-00770(15K)-R2R–01250(22K)-R2R FR-A840-00470(18.5K)-R2R–01800(55K)-R2R Brake resistor DC reactor Brake resistor (FR-HEL) DC reactor (FR-ABR) *7,*8 Brake unit (FR-HEL) (option) Source logic Brake unit (option) Main circuit terminal Jumper Earth Control circuit terminal Jumper Jumper Earth...
  • Page 12 WIRING For the FR-A820-03800(75K)-R2R or higher, and the FR-A840-02160(75K)-R2R or higher, or if using a motor with a capacity of 75 kW or higher, always connect a DC reactor (FR-HEL), which is available as an option. (When selecting a DC reactor, refer to page 48, and select one suitable for the applicable motor capacity.) When a DC reactor is connected to the FR-A820-03160(55K)-R2R or lower or the FR-A840-01800(55K)-R2R or lower, if a jumper is installed across the terminals P1 and P/+, remove the jumper before installing the DC reactor.
  • Page 13 WIRING  FM type FR-A820-00770(15K)-R2R–01250(22K)-R2R FR-A840-00470(18.5K)-R2R–01800(55K)-R2R DC reactor Brake resistor (FR-HEL) Brake resistor DC reactor (FR-ABR) Brake unit *7,*8 (FR-HEL) (option) Sink logic Brake unit (option) Main circuit terminal Jumper Earth Control circuit terminal Jumper Jumper Earth Inrush current limit circuit MCCB R/L1 Inrush current...
  • Page 14 WIRING For the FR-A820-03800(75K)-R2R or higher, and the FR-A840-02160(75K)-R2R or higher, or if using a motor with a capacity of 75 kW or higher, always connect a DC reactor (FR-HEL), which is available as an option. (When selecting a DC reactor, refer to page 48, and select one suitable for the applicable motor capacity.) When a DC reactor is connected to the FR-A820-03160(55K)-R2R or lower or the FR-A840-01800(55K)-R2R or lower, if a jumper is installed across the terminals P1 and P/+, remove the jumper before installing the DC reactor.
  • Page 15 WIRING 2.1.2 FR-A842(-E)-R2R  CA type Source logic Main circuit terminal Control circuit terminal Brake unit (option) Converter unit Motor R/L1 S/L2 T/L3 Jumper R1/L11 Earth (Ground) S1/L21 Main circuit Earth (Ground) Control circuit Control input signals Relay output (No voltage input allowed) Forward rotation start Reverse rotation start Relay output 1 (Alarm...
  • Page 16 WIRING The terminals R1/L11 and S1/L21 are connected to the terminals P/+ and N/– with a jumper respectively. When using separate power supply for the control circuit, remove the jumper between R1/L11 and S1/L21. The function of these terminals can be changed with the input terminal assignment (Pr. 178 to Pr. 189). (Refer to page 29.) Terminal JOG is also used as the pulse train input terminal.
  • Page 17 WIRING  FM type Sink logic Main circuit terminal Control circuit terminal Brake unit (option) Converter unit Motor R/L1 S/L2 T/L3 Jumper Earth (Ground) R1/L11 S1/L21 Main circuit Earth Ground) Control circuit Relay output Control input signals (No voltage input allowed) Forward rotation start Reverse rotation start Relay output 1 (Alarm output)
  • Page 18 WIRING The terminals R1/L11 and S1/L21 are connected to the terminals P/+ and N/– with a jumper respectively. When using separate power supply for the control circuit, remove the jumper between R1/L11 and S1/L21. The function of these terminals can be changed with the input terminal assignment (Pr. 178 to Pr. 189). (Refer to page 29.) Terminal JOG is also used as the pulse train input terminal.
  • Page 19 WIRING 2.2 Main circuit terminal 2.2.1 Terminal layout and wiring FR-A820-00046(0.4K)-R2R, 00077(0.75K)-R2R FR-A820-00105(1.5K)-R2R to 00250(3.7K)-R2R FR-A820-00340(5.5K)-R2R, 00490(7.5K)-R2R FR-A840-00023(0.4K)-R2R to 00126(3.7K)-R2R FR-A840-00170(5.5K)-R2R, 00250(7.5K)-R2R Jumper P/+ PR Jumper Jumper Jumper R1/L11 S1/L21 R/L1 S/L2 T/L3 Jumper R/L1 S/L2 T/L3 Jumper R/L1 S/L2 T/L3 R1/L11 S1/L21 R1/L11 S1/L21 Charge lamp...
  • Page 20 WIRING The following diagram shows the positions of R1/L11, S1/L21, and the charge lamp. Charge lamp Jumper R1/L11 S1/L21 The terminals P3 and PR of the FR-A820-01540(30K)-R2R are not equipped with screws. Do not connect anything to these. When an option other than the DC reactor must be connected to terminal P/+, use terminal P/+ (for option connection). CAUTION O The power supply cables must be connected to R/L1, S/L2, T/L3.
  • Page 21 WIRING 2.3 Wiring fundamentals 2.3.1 Cable size Select the recommended cable size to ensure that a voltage drop will be 2% max. If the wiring distance is long between the inverter and motor, a main circuit cable voltage drop will cause the motor torque to decrease especially at a low speed.
  • Page 22 WIRING 400 V class, FR-A840 (440 V input power supply, ND rating, without a power factor improving AC or DC reactor) Cable gauge Applicable Crimp terminal Tightening Terminal HIV, etc. [mm²] AWG/MCM PVC, etc. [mm²] inverter type Torque screw size R/L1, R/L1, Earthing...
  • Page 23 WIRING For the FR-A820-03160(55K)-R2R or lower and the FR-A840-01800(55K)-R2R or lower, it is the gauge of a cable (HIV cable (600 V class heat- resistant PVC insulated wire), etc.) with the continuous maximum permissible temperature of 75 °C. Assumes that the surrounding air temperature is 50 °C or less and the wiring distance is 20 m or less.
  • Page 24 WIRING 2.3.2 Total wiring length  With general-purpose motor Connect one or more general-purpose motors within the total wiring length shown in the following table. (The wiring length should be 100 m or less under vector control.) FR-A820-00105(1.5K)-R2R or higher, Pr.
  • Page 25 WIRING 2.4 Control circuit terminals 2.4.1 Terminal layout Recommended cable 1 F/C +24 SD So SOC S1 S2 PC gauge: 0.3 to 0.75 mm² 5 10E 10 SE SE SU IPF OL FU PC RL RM RH RT AU STP MRS RES SD SD STF STR JOG (X10)
  • Page 26 WIRING Insert the wires into a socket. When using a single wire or stranded wires without a blade terminal, push the open/close button all the way down with a flathead screwdriver, and insert the wire. Open/close button Flathead screwdriver O Wire removal Pull the wire while pushing the open/close button all the way down firmly with a flathead screwdriver.
  • Page 27 WIRING 2.4.4 Control logic (sink/source) change Change the control logic of input signals as necessary. To change the control logic, change the jumper connector position on the control circuit board. Connect the jumper connector to the connector pin of the desired control logic. O The control logic of input signals is initially set to the sink logic (SINK) for the FM type.
  • Page 28 WIRING 2.5 Safety stop function 2.5.1 Function description The terminals related to the safety stop function are shown below. Terminal symbol Terminal function description Channel 1 Between S1 and SIC Open: In safety stop mode For input of the safety stop Short: Other than the safety stop mode Channel 2 Between S2 and SIC...
  • Page 29 WIRING 2.5.3 Safety stop function operation Output Output Internal *1, *2 Operation panel indication Input terminal Inverter operation terminal *8, *9, *10 signal Input power safety circuit enable signal status So (SO) SAFE E.SAF Output shutoff — — — Not displayed Not displayed (Safe state) Drive enabled Normal...
  • Page 30: Failsafe Of The System Which Uses The Inverter

    Although Mitsubishi Electric assures best quality products, provide an interlock which uses inverter status output signals to pre- vent accidents such as damage to machine when the inverter fails for some reason.
  • Page 31: Precautions For Use Of The Inverter

    4 PRECAUTIONS FOR USE OF THE INVERTER The FR-A800 series is a highly reliable product, but incorrect peripheral circuit making or operation/handling method may shorten the product life or damage the product. Before starting operation, always recheck the following items: O Use crimping terminals with insulation sleeve to wire the power supply and motor.
  • Page 32 PRECAUTIONS FOR USE OF THE INVERTER O FR-A800 models only: Across terminals P/+ and PR, connect only an external brake resistor. Do not connect a mechanical brake. O FR-A842 models (Separated converter type) only: Correct connection of the converter unit and the inverter –...
  • Page 33: Basic Operation

    STOP/RESET key Resets the inverter when the protection function is activated. The setting dial of the Mitsubishi Electric inverters. Turn the setting dial to change the setting of frequency or parameter etc. Press the setting dial to perform the following operations:...
  • Page 34 BASIC OPERATION 5.1.2 Basic operation Operation mode switchover/frequency setting External operation mode (At power-ON) PU operation mode PU JOG operation mode Alternate display Example Frequency setting has been written and Value change completed. Second screen Third screen (Output current monitor) (Output voltage monitor) First screen (Output frequency monitor) *2...
  • Page 35 BASIC OPERATION 5.2 Parameter list For simple variable-speed operation of the inverter, the initial values of the parameters may be used as they are. Set the necessary parameters to meet the load and operational specifications. Parameter setting, change and check can be performed from the operation panel (FR-DU08).
  • Page 36 BASIC OPERATION Parameter Name Setting range Initial value Parameter Name Setting range Initial value Special regenerative Frequency jump 3A 9999 0 to 590 Hz, 9999 0 to 100% brake duty Frequency jump 3B 9999 0 to 590 Hz, 9999 0, 1, 3 to 6, 13 to Speed display 0, 1 to 9998 16, 20, 23, 24, 30,...
  • Page 37 BASIC OPERATION Parameter Name Setting range Initial value Parameter Name Setting range Initial value 0 to 50 , PU communication 0 to 150 ms, 9999 9999 waiting time setting 9999 Motor constant (R1) 9999 0 to 400 m, PU communication CR/ 0 to 2 9999 LF selection...
  • Page 38 BASIC OPERATION Parameter Name Setting range Initial value Parameter Name Setting range Initial value RT signal function RL terminal function validity condition selection 0, 10 selection RM terminal function Stall prevention selection 0 to 31, 100, 101 operation selection RH terminal function selection OL signal output timer 0 to 25 s, 9999...
  • Page 39 BASIC OPERATION Parameter Name Setting range Initial value Parameter Name Setting range Initial value Terminal 1 added Line speed monitoring 0 to 6553.4 m/ 1000 m/min compensation amount reference 0 to 100% (terminal 4) Actual line speed 9999 0 to 100%, 9999 Cooling fan operation voltage/current gain 0, 1, 101 to 105...
  • Page 40 BASIC OPERATION Parameter Name Setting range Initial value Parameter Name Setting range Initial value Line speed command 0 to 8, 10 to 16, RA1 output selection 0 to 65535 9999 25, 26, 30 to 35, digital input bias 39 to 48, 55, 64, Line speed command 68, 79, 80, 85 to 65535...
  • Page 41 BASIC OPERATION Parameter Name Setting range Initial value Parameter Name Setting range Initial value Inverter operation 0 to 6000 mH, 0, 1 lock mode setting Second motor 9999 9999 constant (L2) Pre-scale function 0 to 400 mH, 0 to 5 selection 9999 Second motor...
  • Page 42 BASIC OPERATION Parameter Name Setting range Initial value Parameter Name Setting range Initial value Fourth PID differential Protocol selection 0, 1 time for values below 9999 0.01 to 10 s, 9999 NET mode operation set point 0, 1, 5, command source 9999 9999 Integral control...
  • Page 43 BASIC OPERATION Parameter Name Setting range Initial value Parameter Name Setting range Initial value Power failure stop Analog remote output 800 to 1200% 1000% external signal input 0, 1 selection Analog remote output 1000% 800 to 1200% Motor permissible load 150% 110 to 250% level...
  • Page 44 BASIC OPERATION Parameter Name Setting range Initial value Parameter Name Setting range Initial value Empty reel inertia Easy gain tuning 10 to 999, 9999 9999 1 to 15 (integer) response level setting Empty reel inertia Easy gain tuning 0 to 7, 101 to 104, 9999 0 to 2 (exponent)
  • Page 45 BASIC OPERATION Parameter Name Setting range Initial value Parameter Name Setting range Initial value Control terminal Regeneration option-Encoder avoidance operation 0, 1, 100, 101 0 to 2 rotation direction selection Regeneration Speed deviation time 380 V DC 0 to 100 s avoidance operation 300 to 1000 V Excitation ratio...
  • Page 46 BASIC OPERATION Parameter Name Setting range Initial value Parameter Name Setting range Initial value Terminal 2 frequency Current output gain (903) (931) 0 to 590 Hz 0 to 100% 60/50 Hz —/100 % setting gain frequency signal Terminal 2 frequency Current output gain (903) (931)
  • Page 47 BASIC OPERATION Parameter Name Setting range Initial value Parameter Name Setting range Initial value Digital source 0 to 59, 1038 100 to 159, selection (1ch) 200 to 259, Digital source 300 to 359, 1039 selection (2ch) 400 to 459, 500 to 559, Digital source 1040 600 to 659,...
  • Page 48 BASIC OPERATION Parameter Name Setting range Initial value Parameter Name Setting range Initial value Minimum winding 120 Hz Per-unit speed control 1242 1 to 6553 mm 1 mm 1121 0 to 400 Hz diameter 4 reference frequency 60 Hz Gear ratio numerator 1243 Station number in 1 to 65534...
  • Page 49 BASIC OPERATION Parameter Name Setting range Initial value Parameter Name Setting range Initial value Line multi-speed Winding length 0 to 6553.4 m/ 1269 0 m/min 1346 setting (speed 5) detection (upper 4 0 (m 0 to 9999 (m digits) Line multi-speed 0 to 6553.4 m/ 1270 0 m/min...
  • Page 50 BASIC OPERATION Parameter Name Setting range Initial value Parameter Name Setting range Initial value Ethernet signal loss Ethernet command 1431 detection function source selection IP 0 to 3 1454 9999 0 to 255, 9999 selection address 4 range specification Ethernet 1432 communication check *19 Keepalive time...
  • Page 51: Troubleshooting

    6 TROUBLESHOOTING When a fault occurs in the inverter, the protective function activates, and the PU display automatically changes to one of the fault or alarm indications listed on page 46. If the fault does not correspond to any of the following errors or if you have any other problem, please contact your sales repre- sentative.
  • Page 52 TROUBLESHOOTING 6.1 Reset method of protective function The inverter can be reset by performing any of the following operations. Note that the internal thermal integrated value of the electronic thermal relay function and the number of retries are cleared (erased) by resetting the inverter. Inverter recovers about 1s after reset is cancelled.
  • Page 53 TROUBLESHOOTING Data Data Operation panel indication Name Operation panel indication Name code code Motor overload trip (electronic Abnormal output current E.THM E.CDO thermal relay function) (H31) detection (HC4) E.FIN Heatsink overheat Inrush current limit circuit fault E.IOH (H40) (HC5) Instantaneous power failure E.IPF Communication fault (inverter) E.SER...
  • Page 54: Specifications

    15.5 15.5 The applicable motor capacity indicated is the maximum capacity applicable for use of the Mitsubishi Electric 4-pole standard motor. For the SND rating, the carrier frequency is always 2 kHz. The 0.2 kW motor capacity is applicable under V/F control only.
  • Page 55 SPECIFICATIONS The rated input current indicates a value at a rated output voltage. The impedance at the power supply side (including those of the input reactor and cables) affects the rated input current. The power supply capacity is the value when at the rated output current. It varies by the impedance at the power supply side (including those of the input reactor and cables).
  • Page 56 Forced air cooling Approx. mass [kg] The applicable motor capacity indicated is the maximum capacity applicable for use of the Mitsubishi Electric 4-pole standard motor. For the SND rating, the carrier frequency is always 2 kHz. The 0.2 kW motor capacity is applicable under V/F control only.
  • Page 57 SPECIFICATIONS The rated input current indicates a value at a rated output voltage. The impedance at the power supply side (including those of the input reactor and cables) affects the rated input current. The power supply capacity is the value when at the rated output current. It varies by the impedance at the power supply side (including those of the input reactor and cables).
  • Page 58 Forced air cooling Approx. mass [kg] The applicable motor capacity indicated is the maximum capacity applicable for use of the Mitsubishi Electric 4-pole standard motor. For the SND rating, the carrier frequency is always 2 kHz. The rated output capacity indicated assumes that the output voltage is 440 V.
  • Page 59 SPECIFICATIONS 7.2 Outline dimensions FR-A820-00046(0.4K)-R2R to 04750(90K)-R2R FR-A840-04320(160K)-R2R to 06830(280K)-R2R FR-A820-00046(0.4K) to 04750(90K) FR-A840-04320(160K) to 06830(280K) FR-A840-00023(0.4K)-R2R to 03610(132K)-R2R FR-A840-00023(0.4K) to 03610(132K) 3-φC 2-φC (Unit: mm) Inverter type FR-A820-00046(0.4K)-R2R FR-A820-00077(0.75K)-R2R FR-A820-00105(1.5K)-R2R FR-A820-00167(2.2K)-R2R FR-A820-00250(3.7K)-R2R FR-A820-00340(5.5K)-R2R FR-A820-00490(7.5K)-R2R FR-A820-00630(11K)-R2R FR-A820-00770(15K)-R2R FR-A820-00930(18.5K)-R2R FR-A820-01250(22K)-R2R FR-A820-01540(30K)-R2R FR-A820-01870(37K)-R2R FR-A820-02330(45K)-R2R FR-A820-03160(55K)-R2R...
  • Page 60 SPECIFICATIONS FR-A842-07700(315K)-R2R to 12120(500K)-R2R 3-ØC (Unit: mm) Inverter type FR-A842-07700(315K) -R2R 1330 1300 FR-A842-08660(355K) -R2R FR-A842-09620(400K) -R2R FR-A842-10940(450K) 1580 1550 -R2R FR-A842-12120(500K) -R2R For dimensions of the converter unit (FR-CC2) refer to the FR-CC2 Instruction Manual.
  • Page 61: Aappendix

    CE marking. O The authorized representative in the EU The authorized representative in the EU is shown below: Name: Mitsubishi Electric Europe B.V. Address: Mitsubishi-Electric-Platz 1, 40882 Ratingen, Germany NOTE We declare that this inverter conforms with the EMC Directive in industrial environments and affix the CE marking on the inverter.
  • Page 62 APPENDIX A.1.2 Low Voltage Directive We have self-confirmed our inverters as products compliant to the Low Voltage Directive (conforming standard EN 61800-5-1) and place the CE mark on the inverters. Outline of instructions O Do not use an earth leakage current breaker as an electric shock protector without connecting the equipment to the earth. Connect the equipment to the earth securely.
  • Page 63 APPENDIX Wiring protection For installation Class T, Class J, Class CC, or Class L fuse, or UL 489 Molded Case Circuit Breaker (MCCB) according to the local direc- tives must be provided. For the FR-A820 series, Class T, Class J, or Class CC fuse, or UL 489 Molded Case Circuit Breaker (MCCB) must be provided. 00046 00077 00105...
  • Page 64 Manufacturer Rated voltage, V AC MMP-T32 Mitsubishi Electric Corp. 480Y/277 Suitable for use in a circuit capable of delivering not more than 50 or 25 kA rms symmetrical amperes, 480Y/277 volts maximum when protected by the type E combination motor controllers indicated in the above table.
  • Page 65 30Hz or more O Operation region 20Hz When using the Mitsubishi Electric constant-torque motor Region on the right of 20Hz 10Hz characteristic curve set one of "1", "13" to "16", "50", "53", "54" in Pr. 71. For FR-...
  • Page 66 Fax: +356 (0)21 / 697 817 Phone: +1 (847) 478-2100 Fax: +1 (847) 478-0328 Mitsubishi Electric Europe B.V. / FA - European Business Group / Mitsubishi-Electric-Platz 1 / D-40882 Ratingen / Germany / Tel.: +49(0)2102-4860 / Fax: +49(0)2102-4861120 / info@mitsubishi-automation.com / https://eu3a.mitsubishielectric.com...