Mitsubishi Electric FR-A820-00046 (0.4K) Instruction Manual page 53

Fr-a800 series
Hide thumbs Also See for FR-A820-00046 (0.4K):
Table of Contents

Advertisement

 Type CA (FR-A800-GF)
Source logic
Main circuit terminal
Control circuit terminal
MCCB
Three-phase
AC power
supply
Control input signals
(No voltage input allowed)∗3
Forward rotation start
Reverse rotation start
Start self-holding selection
High speed
Multi-speed
Middle speed
selection
Low speed
Jog operation
Second function selection
Output stop
Terminal 4 input selection
(Current input selection)
Selection of automatic restart
after instantaneous power failure
Common for external power
supply transistor
Contact input common
24VDC power supply
24V external power
supply input
Common terminal
Frequency setting signals (Analog)
Frequency setting
potentiometer
1/2W1kΩ∗6
Auxiliary
input
Terminal 4 input
(Current input)
Safety stop signal
Safety stop input (Channel 1)
Safety stop input (Channel 2)
Safety stop input common
52
2. INSTALLATION AND WIRING
2.4 Terminal connection diagrams
DC reactor
(FR-HEL)∗1
Jumper
Earth
(Ground)
P1
MC
R/L1
S/L2
T/L3
R1/L11
Jumper
∗2
S1/L21
Earth
(Ground)
Control circuit
STF
STR
STP(STOP)
RH
RM
RL
∗4
JOG
RT
MRS
RES
Reset
AU
CS
SD
PC
+24
SD
10E(+10V)
10(+5V)
3
DC0 to 5V
2
2
DC0 to 10V selectable
DC0 to 20mA
5
1
(Analog common)
DC0 to ±10V
(+)
1
DC0 to ±5V selectable
(-)
DC4 to 20mA
(+)
4
DC0 to 5V
(-)
DC0 to 10V
PU connector
USB A connector
USB mini B connector
24V
Shorting wire
PC
S1
Output shutoff
S2
circuit
SIC
SD
Brake resistor
(FR-ABR)∗7∗8
Brake unit
R
(Option)
Jumper
P/+
PX
PR
N/-
R
U
Inrush current
V
limit circuit
W
ON
EMC filter
ON/OFF
connector
OFF
Main circuit
C1
B1
A1
C2
B2
A2
RUN
SU
IPF
OL
FU
SE
24V
PORT 1
PORT 2
Connector 2
Connector 3
Voltage/current
∗5
input switch
ON
F/C
OFF
2
4
(CA)
Initial value
∗5
AM
Initial value
5
∗5
Initial value
TXD+
∗5
selectable
TXD-
RXD+
RXD-
GND
(SG)
Terminating
VCC
resistor
So
(SO)
SOC
FR-A820-00770(15K) to 01250(22K),
FR-A840-00470(18.5K) to 01800(55K)
DC reactor
(FR-HEL)∗1
Jumper
Earth
∗9
(Ground)
P1
P/+
P3
Inrush
current
limit circuit
Motor
M
Earth (Ground)
Relay output∗10
Relay output 1
(Fault output)
Relay output 2
Open collector output∗11
Running
Up to frequency
Instantaneous
power failure
Overload
Frequency detection
Open collector output common
Sink/source common
CC-Link IE Field Network
communication connector
Connector for plug-in option
connection
(+)
Analog current output
(0 to 20mADC)
(-)
(+)
Analog signal output
(DC0 to ±10V)
(-)
RS-485 terminals
Data
transmission
Data
reception
GND
5V
(Permissible load current 100mA)
Safety monitor output
Safety monitor output common
Brake resistor∗8
Brake unit
(Option)
R
PR
N/-

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fr-a820-00167 (2.2k)Fr-a820-00046-gf (0.4k)Fr-a820-00250 (3.7k)Fr-a820-00105-gf (1.5k)Fr-a820-00077 (0.75k)Fr-a820-00250-gf (3.7k) ... Show all

Table of Contents