NOTE
• If "9999" is set, tuning data will be invalid. The MM-CF constant is used for the IPM motor MM-CF, and the inverter internal
constant is used for a PM motor other than MM-CF.
• To change a motor induced voltage constant of PM motors, the setting in Pr.706 Induced voltage constant (phi f) or Pr.738
Second motor induced voltage constant (phi f) must be changed. If the constant after the change exceeds the setting range
of Pr.706 or Pr.738 (0 to 5000 mV (rad/s)), set Pr.1412 Motor induced voltage constant (phi f) exponent or Pr.1413
Second motor induced voltage constant (phi f) exponent. Set a value in the exponent n in the formula, Pr.706 (Pr.738) ×
10n [mV (rad/s)], to set the induced voltage constant (phi f).
• When Pr.71 (Pr.450) = "8093, 8094, 9093, or 9094", or Pr.1412 (Pr.1413) = "9999", the motor induced voltage constant is as
set in Pr.706 (Pr.738). (No exponent setting)
 Changing the motor constants (when setting a motor constants in the
internal data of the inverter)
• Set Pr.71 as follows.
IPM motor
SPM motor
• Set desired values as the motor constant parameters. The displayed increments of the read motor constants can be
changed with Pr.684 Tuning data unit switchover. Setting Pr.684 = "1" disables parameter setting changes.
First motor
Second
Pr.
motor Pr.
90
458
92
460
93
461
706
738
859
860
1412
1413
*1
For the FR-A820-03160(55K) or lower, and FR-A840-01800(55K) or lower.
*2
For the FR-A820-03800(75K) or higher, and FR-A840-02160(75K) or higher.
NOTE
• As the motor constants measured in the offline auto tuning have been converted into internal data (****), refer to the following
setting example when making setting. (The value displayed has been converted into a value for internal use. Therefore, simple
addition of a value to the displayed value does not bring the desired effect.)
Setting example: to slightly increase the Pr.90 value (5%)
When "2516" is displayed for Pr.90, set 2642 (2516 × 1.05 = 2641.8) in Pr.90.
• If "9999" is set, tuning data will be invalid. The MM-CF constant is used for the IPM motor MM-CF, and the inverter internal
constant is used for a PM motor other than MM-CF.
• To change a motor induced voltage constant of PM motors, the setting in Pr.706 Induced voltage constant (phi f) or Pr.738
Second motor induced voltage constant (phi f) must be changed. If the constant after the change exceeds the setting range
of Pr.706 or Pr.738 (0 to 5000 mV (rad/s)), set Pr.1412 Motor induced voltage constant (phi f) exponent or Pr.1413 Second
motor induced voltage constant (phi f) exponent. Set a value in the exponent n in the formula, Pr.706 (Pr.738) × 10n [mV
(rad/s)], to set the induced voltage constant (phi f).
• When Pr.71 (Pr.450) = "8093, 8094, 9093, or 9094", or Pr.1412 (Pr.1413) = "9999", the motor induced voltage constant is as
set in Pr.706 (Pr.738). (No exponent setting)
526
5. PARAMETERS
5.13 (C) Motor constant parameters
Motor
MM-CF
Other than MM-CF
Pr.684 = 0 (initial value)
Name
Setting range
Motor constant (R1)
Motor constant (L1)/d-
axis inductance (Ld)
Motor constant (L2)/q-
axis inductance (Lq)
0 to ***, 9999
Induced voltage
constant (phi f)
Torque current/Rated
PM motor current
Motor induced voltage
constant (phi f)
exponent
333 (334)
8093 (8094)
9093 (9094)
Pr.684 = 1
Setting
Range indication
increments
0 to 50 Ω, 9999
0 to 400 mΩ, 9999
0 to 500 mH, 9999
0 to 50 mH, 9999
0 to 500 mH, 9999
0 to 50 mH, 9999
1
0 to 5000 mV (rad/s),
9999
0 to 500 A, 9999
0 to 3600 A, 9999
0 to 2, 9999
Pr.71 setting
Initial
Unit
value
indication
*1
*1
0.001 Ω
*2
*2
0.01 mΩ
*1
*1
0.01 mH
*2
*2
0.001 mH
*1
*1
0.01 mH
*2
*2
0.001 mH
9999
0.1 mV (rad/s)
*1
*1
0.01 A
*2
*2
0.1 A
1