Parameter
6.24

CC-Link IE Field Network Basic

The CC-Link IE Field Network Basic enables CC-Link IE communication using the general-purpose
Ethernet-based technology. The CC-Link IE Field Network Basic is suited to small-scale equipment for
which high-speed control is not necessary, and can coexist with the standard Ethernet TCP/IP (HTTP,
FTP, etc.).
Pr. No.
Name
Frequency command sign
541
selection
544
CC-Link extended setting
The setting is applied after an inverter reset or power-ON.
Communication specifications
Item
Transmission speed
Communication method
Connectable units
Topology
Number of occupied stations
Maximum number of links per station
Reference response time
Tab. 6-140: Specifications of the CC-Link IE Field Network Basic communication
The reference response time is the communication time from when the inverter receives a com-
mand from the master until the inverter returns the response to the master
Initial setting
● To select the CC-Link IE Field Network Basic for the application, set "10" in any of Pr. 833 to Pr. 835
"Ethernet function selection 1 to 3". (Refer to page 6-285.)
● To limit the network devices that send the command through the Ethernet network (CC-Link IE
Field Network Basic), set the range of IP addresses (Pr. 844 to Pr. 849). (Refer to page 6-289.)
● Use Pr. 852 "Ethernet communication check time interval" to set the interval of the check time (for
signal loss detection) for all devices with IP addresses in the range specified for "Ethernet com-
mand source selection" (Pr.844 to Pr.849). (Refer to page 6-290.)
NOTE
When Pr. 852 "Ethernet communication check time interval"
work Basic is used, the Ethernet communication fault (E.OP1) is activated in the following cases:
the data addressed to the own station is not received for the predetermined timeout period or
longer, or the status bit of the cyclic transmission addressed to the own station turns OFF (when
the master inverter gives a command to stop the cyclic transmission). (For the details of the time-
out period, status bit of the cyclic transmission, and command to stop the cyclic transmission, refer
to the Instruction Manual of the master controller which supports the CC-Link IE Field Network
Basic.)
FR-E700 SC EC/ENE
Initial Value
Setting Range Description
0
Frequency command without sign
0
1
Frequency command with sign
The function of the remote registers can be
0
0/1/12/14/18
extended when the CC-Link IE Field Network Basic
is used.
RX
RY
RWr
RWw
CC-Link IE Field Network Basic
Parameters referred to
Description
100 Mbps
UDP/IP
Master: 1
Slave: up to 64
Star
1
64 (8 bytes)
64 (8 bytes)
32 (64 bytes)
32 (64 bytes)
Within 15 ms
9999 and the CC-Link IE Field Net-
Refer to
Section
6 - 349