• Set Pr.154 = "10 or 11" when the overvoltage protective function (E.OV[]) is activated during stall prevention operation in
an application with large load inertia. Note that turning OFF the start signal (STF/STR) or varying the frequency command
during stall prevention operation may delay the acceleration/deceleration start.
Pr.154
0
Enabled
1 (initial value)
—
10
Enabled
11
—
CAUTION
• Do not set the stall prevention operation current too low.
Doing so will reduce the generated torque.
• Be sure to perform the test operation.
Stall prevention operation during acceleration may extend the acceleration time.
Stall prevention operation during constant-speed operation may cause sudden speed changes.
Stall prevention operation during deceleration may extend the deceleration time.
Parameters referred to
Pr.22 Torque limit
levelpage 235
Pr.73 Analog input
selectionpage 473
Pr.178 to Pr.189 (Input terminal function
Pr.190 to Pr.196 (Output terminal function
Pr.858 Terminal 4 function assignment, Pr.868 Terminal 1 function
416
5. PARAMETERS
5.10 (H) Protective function parameter
E.OC[] countermeasure
selection)page 496
selection)page 450
E.OV[] countermeasure
—
—
Enabled
Enabled
assignmentpage 477