Initial Setting For Cc-Link Ie Field Network Basic - Mitsubishi Electric FR-E800 Instruction Manual (Communication

Hide thumbs Also See for FR-E800:
Table of Contents

Advertisement

*1
The LED on either LINK1 or LINK2 will blink depending on the port (port 1 or 2) the Ethernet cable is connected to.
NOTE
• If the FR-E800-(SC)E cannot be detected, on the menu bar select [Diagnostics (D)] > [CC Link IEF Basic Diagnostics]. The
"CC Link IEF Basic Diagnostics" window will be displayed. The network status or fault records can be checked.
2.6.3

Initial setting for CC-Link IE Field Network Basic

Use the following parameters to perform required settings for Ethernet communication between the inverter and other devices.
To make communication between other devices and the inverter, perform the initial settings of the inverter parameters to match
the communication specifications of the devices. Data communication cannot be made if the initial settings are not made or if
there is any setting error.
Pr.
Name
1427
Ethernet function
*1
selection 1
N630
1428
Ethernet function
*1
selection 2
N631
1429
Ethernet function
*1
selection 3
N632
1430
Ethernet function
*1
selection 4
N633
1432
Ethernet communication
N644
check time interval
Initial
Setting range
value
5001
502, 5000 to 5002, 5006
45237
to 5008, 5010 to 5013,
*3
*2
9999, 34962
, 44818
*2
45238
45237, 45238, 47808
61450
9999
0
1.5 s
0.1 to 999.8 s
9999
Description
,
Set the application, protocol, etc.
,
Ethernet communication is available, but the inverter output is
shut off in the NET operation mode.
Set the interval of the communication check (signal loss
detection) time for all devices with IP addresses in the range
specified for Ethernet command source selection (Pr.1449 to
Pr.1454).
If a no-communication state persists for longer than the
permissible time, the inverter output will be shut off.
No communication check (signal loss detection)
2.6 CC-Link IE Field Network Basic
55
2. Ethernet Communication
1
2
3
4
5
6
7
8
9
10

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

E820s

Table of Contents