Actuator Configuration Commands - LEGRAND Server Technology PRO4X User Manual

Hide thumbs Also See for Server Technology PRO4X:
Table of Contents

Advertisement

Sensor types
airPressure
airFlow
vibration
Note: If the specified sensor type does not match the type of the specified environmental sensor, this
error message appears: "Specified sensor type 'XXX' does not match the sensor's type
(<sensortype>)," where XXX is the specified sensor type, and <sensortype> is the correct sensor type.
<option> is one of the options: enable, disable or a numeric value.
Option
Description
enable
Enables the specified threshold for a specific environmental
sensor.
disable
Disables the specified threshold for a specific environmental
sensor.
A numeric
Sets a value for the specified threshold of a specific
value
environmental sensor and enables this threshold at the same
time.
<hy_value> is a numeric value that is assigned to the hysteresis for the specified environmental
sensor.
<as_value> is a number in samples that is assigned to the assertion timeout for the specified
environmental sensor. It ranges between 1 and 100.

Actuator Configuration Commands

An actuator configuration command begins with actuator. You can configure the name and location
parameters of an individual actuator.
You can configure various parameters for one actuator at a time.
Change the name:
config:#
actuator <n> name "<name>"
Set the X coordinate:
config:#
actuator <n> xlabel "<coordinate>"
Description
Air pressure sensors
Air flow sensors
Vibration sensors
515

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Server Technology PRO4X and is the answer not in the manual?

Table of Contents