Setting the Outlet Relay Behavior
This section applies to outlet-switching capable models only.
This command syntax determines the relay behavior of all outlets on a PRO4X model.
config:#
pdu relayBehaviorOnPowerLoss <option>
Variables:
<option> is one of the options: latching or nonLatching
Setting the Outlet Power-On Sequence
This section applies to outlet-switching capable models only.
This command sets the outlet power-on sequence when the PDU powers up.
config:#
Variables:
<option> is one of the options: default, or a comma-separated list of outlet numbers.
Option
default
A comma-
separated list of
outlet numbers
Note: Power-on sequencing is disabled in the latching mode.
Setting the Outlet Power-On Sequence Delay
This section applies to outlet-switching capable models only.
This command sets the delays (in seconds) for outlets when turning on all outlets in sequence.
config:# pdu outletSequenceDelay <outlet1>:<delay1>;<outlet2>:<delay2>;
<outlet3>:<delay3>;...
414
pdu outletSequence <option>
Description
All outlets are switched ON in the ASCENDING order (from
outlet 1 to the final outlet) when the PRO4X powers up.
All outlets are switched ON in the order you specify using
the comma-separated list.
The list must include all outlets on the PDU.