3) Make changes to the remaining fields as needed, then click Save.
Section
Description
Auto Relock
•
•
Time
Door sensor
•
•
polarity
•
•
•
•
•
•
Relock on
•
•
Handle Close
Connected
•
•
Device
368
Specify how long the lock can remain open after someone opens
the door handle lock via smart card or remote control without the
handle being opened during that period. When the timeout
expires, the lock will be automatically closed. Default is 600
seconds (that is, 10 minutes).
Choose the correct setting based on the type of contact closure
sensors used to monitor the door:
Normally closed: The contact is closed (conducting) when the
door is closed and open (not conducting) when the door is open.
Default.
Normally open: The contact is not conducting when the door is
closed and is conducting when the door is open.
Note: For both normally closed and normally open sensors, the
reported state is "open" when the door is open and "closed"
when the door is closed.
This setting controls auto-locking. Select "Only if door closed" to
delay auto-locking until "Door State" and "Door Handel State" are
both verified as "Closed". Select "Always" to relock automatically.
If your door handle has a connected device, such as a keypad,
select it from the list.