Set the Lower Critical threshold for an outlet sensor:
config:# sensor outlet <n> <sensor type> lowerCritical <option>
Set the Lower Warning threshold for an outlet sensor:
config:#
sensor outlet <n> <sensor type> lowerWarning <option>
Set the deassertion hysteresis for an outlet sensor:
config:#
sensor outlet <n> <sensor type> hysteresis <hy_value>
Set the assertion timeout for an outlet sensor:
config:# sensor outlet <n> <sensor type> assertionTimeout <as_value>
Variables:
<n> is the number of the outlet that you want to configure.
<sensor type> is one of the following sensor types:
Sensor type
current
voltage
activePower
apparentPower
powerFactor
activeEnergy
lineFrequency
Note: If the requested sensor type is not supported, the "Sensor is not available" message is
displayed.
<option> is one of the options: enable, disable or a numeric value.
Option
enable
504
Description
Current sensor
Voltage sensor
Active power sensor
Apparent power sensor
Power factor sensor
Active energy sensor
Line frequency sensor
Description
Enables the specified threshold for a specific outlet sensor.