Example - Default Upper Thresholds for Temperature
It is assumed that your preferred measurement unit for temperature is set to degrees Celsius. Then the
following command sets the default Upper Warning threshold to 20
24
for all temperature sensors.
config:# defaultThresholds temperature upperWarning 20
upperCritical 24

Sensor Threshold Configuration Commands

A sensor configuration command begins with sensor. You can use the commands to configure the
threshold, hysteresis and assertion timeout values for any sensor associated with the following items:
Outlets
Outlet groups
Inlets
Inlet poles (for three-phase PDUs only)
Overcurrent protectors
Environmental sensors
It is permitted to assign a new value to the threshold at any time regardless of whether the threshold
has been enabled.
Note: Your Xerus product may not support all commands.
Commands for Outlet Sensors
A sensor configuration command for outlets begins with sensor outlet.
You can configure various outlet sensor threshold settings at a time by combining multiple commands.
Set the Upper Critical threshold for an outlet sensor:
config:# sensor outlet <n> <sensor type> upperCritical <option>
Set the Upper Warning threshold for an outlet sensor:
config:#
sensor outlet <n> <sensor type> upperWarning <option>
and Upper Critical threshold to
503