1) Log in to the target device, which is of the same model and runs the same firmware as the source
device.
2) Choose Maintenance > Bulk Configuration.
3) In the Restore Bulk Configuration section, click Browse to select the configuration file.
4) Click 'Upload & Restore Bulk Configuration'.
5) Confirm the operation and enter the administrator password, then click Restore.
6) Wait until the login page reappears.
Modifying or Deleting Bulk Configuration Profiles
You can modify or delete any bulk profile except for the built-in one.
Note that a profile that has been set as the default cannot be deleted. To remove it, you have to remove
its default setting first.
Choose Maintenance > Bulk Configuration. A list of profiles displays and then do one of the following.
To modify an existing profile:
1) Click on the row of the wanted profile in the list.
2) Change the settings you want.
3) Click Save.
To delete profiles
1) Select one or multiple profiles, then click the Delete icon
2) Click Delete in the confirmation message.

Backup and Restore of Device Settings

Unlike the bulk configuration file, the backup file contains ALL device settings, including device-specific
data like device names and all network settings. To back up or restore the device settings, you should
use the Backup/Restore feature. To perform bulk configuration among multiple PRO4X devices, use the
Bulk Configuration feature instead.
All PRO4X information is captured in the plain-TEXT-formatted backup file except for the device logs and
TLS certificate.
Backup/Restore can also be completed using other methods. See
Methods
(on page ).