Field
Description
Timer delay
This field appears for the 'Timer' method.
Valid values range between 5 and 10,000 seconds.
Active power
threshold
The field appears for the 'Active power drop' method.
Valid values range between 0 and 21,000 W.
Timeout for
shutdown
This field appears for the 'Active power drop' method.
check
Valid values range between 5 and 10,000 seconds.
The power-off operation is performed only when the active power
value of the selected outlet or outlet group drops below the
'Active power threshold' within the period of time specified in this
field.
If the active power value drops below the 'Active power
threshold' after the specified time expires, the power-off
operation will NOT be performed.
Server Status Checking or Power Control
Not all models supports the shutdown and power control features via the Server Reachability page.
After adding IT equipment for monitoring, all IT devices are listed on the Server Reachability page.
In the beginning, the status of the added IT equipment shows "Waiting for reliable connection," which
means the requested number of consecutive successful or unsuccessful pings has not reached before
PRO4X can declare that the monitored device is reachable or unreachable.
328