inverters
Goodrive35
Function
code
Polarity of output
P06.05
P06.06
Y1 switch-on delay time
P06.07
Y1 switch-off delay time
P06.08
HDO switch-on delay time
P06.09
HDO switch-off delay time
P06.10
RO1 switch-on delay time 0.000~50.000s
P06.11
RO1 switch-off delay time 0.000~50.000s
P06.12
RO2 switch-on delay time 0.000~50.000s
P06.13
RO2 switch-off delay time 0.000~50.000s
The Max. temperature at
P07.38
Digital output terminals
P17.13
7.13 Simple PLC
Simple PLC function is also a multi-step speed generator. The inverter can change the running
frequency, direction to meet the need of processing according to the running time automatically. In
the past, this function needs to be assisted by external PLC, but now the inverter can realize this
function by itself.
The series inverters can control 16-stage speed with 4 groups of ACC/DEC time.
Name
Detailed instruction of parameters
26:Bus voltage established
27: Reserved 28: Pulse superposing 29:
Reserved
30: Positioning finished
31: Spindle returning finished
32: Spindle scaling finished
33: Speed limiting
34: Low bus voltage
35: Reserved
36: Speed/position switching finished
37~40: Reserved
0x00~0x0F
terminals
0.000~50.000s
0.000~50.000s
0.000~50.000s
(valid only when P06.00=1)
0.000~50.000s
(valid only when P06.00=1)
current fault
state
www.barghmaher.ir
Basic operation instruction
226
Default
value
0x00
0.000s
0.000s
0.000s
0.000s
0.000s
0.000s
0.000s
0.000s
0
0