INVT Goodrive 35 Series Operation Manual page 250

Close loop vector control inverter
Hide thumbs Also See for Goodrive 35 Series:
Table of Contents

Advertisement

inverters
Goodrive35
Motor
OL1
overload
Inverter
OL2
overload
Electrical
OL3
overload
Input phase
SPI
loss
Output phase
SPO
loss
Rectifying
OH1
module
overheated
IGBT
OH2
overheated
EF
External fault
The voltage of the power
supply is too low
The motor setting rated
current is incorrect
The motor stall or load
transients is too strong
The acceleration is too fast
Reset the rotating motor
The voltage of the power
supply is too low.
The load is too heavy.
The motor power is too
small.
The inverter will report
overload pre-alarm
according to the set value.
Phase loss or fluctuation of
input R,S,T
U,V,W phase loss input(or
serious asymmetrical three
phase of the load)
Air duct jam or fan damage
Ambient temperature is too
high.
The time of overload running
is too long.
SI external fault input
terminals action
249
www.barghmaher.ir
Fault tracking
Check the power of the supply
line
Reset the rated current of the
motor
Check the load and adjust the
torque lift
Increase the ACC time
Avoid the restarting after
stopping.
Check the power of the supply
line
Select an inverter with bigger
power.
Select a proper motor.
Check the load and the overload
pre-alarm point.
Check input power
Check installation distribution
Check the output distribution
Check the motor and cable
Refer to the overcurrent solution
Redistribute dredge the wind
channel or change the fan
Low the ambient temperature
Check and reconnect
Change the power
Change the power unit
Change the main control panel
Check the external device input