inverters
Goodrive35
Function
Name
code
of the
starting
step of S
curve
DEC time
of the
P01.07
ending
step of S
curve
0: Decelerate to stop: after the stop command
becomes valid, the inverter decelerates to decrease
the output frequency during the set time. When the
P01.08
Stop mode
frequency decreases to P01.15, the inverter stops.
1: Coast to stop: after the stop command becomes
valid, the inverter ceases the output immediately.
And the load coasts to stop at the mechanical inertia.
Starting
The starting frequency of stop braking: the inverter
frequency
will carry on stop DC braking when the frequency is
P01.09
of DC
arrived during the procedure of decelerating to stop.
braking
Demagnetizing time: before the stop DC braking, the
inverter will close output and begin to carry on the
Demagneti
P01.10
DC braking after the waiting time. This function is
zing time
used to avoid the overcurrent fault caused by DC
DC braking
P01.11
braking when the speed is too high.
current
Stop DC braking current: the DC brake added. The
stronger the current, the bigger the DC braking
effect.
DC braking
P01.12
The braking time of stop braking: the retention time
time
of DC brake. If the time is 0, the DC brake is invalid.
The inverter will stop at the set deceleration time.
Detailed instruction of parameters
65
www.barghmaher.ir
Function codes
Default
Modify
value
◎
0.1s
○
0
0.00
○
Hz
○
0.00s
○
0.0%
○
0.0s