inverters
Goodrive35
P04.28
Keypad
Keypad setting voltage
AI1
0
AI2
1
2
AI3
3
HDI
4
5
Multi-stage speed
6
PID
7
8
MODBUS
9
PROFIBUS
10
Erthernet
P04.27(voltage setting channel selection)
CAN
P00.10
Keypad setting frequency
When the user selects the user-defined V/F curve function in Goodrive35 series inverters, they can
set the given channel of voltage and frequency and the corresponding ACC/DEC time, or the two
can combinate to form a real-time curve.
Note: the application of V/F curve separation can be used in many cases with various kinds of
power supply of the inverter. But the users should set and adjust the parameters with caution.
Incorrect parameters may cause damage to the inverter.
Function
code
P00.00
Speed control mode
P00.03
Max. output frequency
Upper limit of the running
P00.04
Lower limit of the running
P00.05
P00.11
Voltage setting
P04.29 voltage ACC time
P04.30 voltage DEC time
Keypad
Frequency setting
AI1
0
AI2
1
2
AI3
3
HDI
4
5
Simple PLC
6
Multi-stage speed
7
8
PID
9
MODBUS
10
PROFIBUS
11
Erthernet
P00.06
A frequency command selection
CAN
Name
Detailed instruction of parameters
0: Sensorless vector control mode 1
1: Sensorless vector control mode 2
2:SVPWM control
3: Close loop vector control mode
P00.04~400.00Hz
P00.05~P00.03
frequency
0.00Hz~P00.04
frequency
ACC time 1
0.0~3600.0s
www.barghmaher.ir
Basic operation instruction
Linear V/F curve
Multi-dots V/F curve
1.3th power of torque V/F curve
1.7th power pf torque V/F curve
2.0th power of torque V/F curve
Self-defined V/F curve
P04.31 output Max. voltage
P04.32 output Mini voltage
P00.11 ACC 1
P00.12 DEC 1
185
0
1
2
3
4
5
P04.00 motor 1V/F curve setting
V /F curve
P00.04 upper limit of the running
frequency
P00.05 lower limit of the running
frequency
PWM output
Default
value
2
50.00Hz
50.00Hz
0.00Hz
Depend
on model