Goodrive35 inverters
Terminal
name
PE
PW
24V
COM
S1
S2
S3
S4
S5
S6
S7
S8
HDI
Terminal
name
HDO
COM
CME
Y1
485+
485-
PE
Grounding terminal
Provide the input switch working power supply from external to
internal.
Voltage range: 12~24V
The inverter provides the power supply for users with a maximum
output current of 200mA
+24V common terminal
Switch input 1
1. Internal impedance:3.3kΩ
Switch input 2
2. 12~30V voltage input is available
Switch input 3
3. The terminal is the dual-direction input
Switch input 4
terminal supporting both NPN and PNP
4. Max input frequency:1kHz
Switch input 5
5. All are programmable digital input
Switch input 6
terminal. User can set the terminal function
Switch input 7
through function codes.
Switch input 8
Except for S1~S8, this terminal can be used as high frequency
input channel.
Max. input frequency:50kHz
1. Switch input: 200mA/30V
2. Output frequency range: 0~50kHz
+24V common terminal
Common terminal of the open collector pole output
1.Swtich capability: 200mA/30V
2.Output frequency range: 0~1kHz
485 communication interface and 485 differential signal interface
If it is the standard 485 communication interface, please use
twisted pairs or shield cable.
Grounding terminal
37
www.barghmaher.ir
Installation guidelines
Description
Description

Hide quick links:

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Goodrive 35 Series and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

This manual is also suitable for:

Gd35-5r5g-4-h1

Table of Contents