INVT Goodrive 35 Series Operation Manual page 134

Close loop vector control inverter
Hide thumbs Also See for Goodrive 35 Series:
Table of Contents

Advertisement

inverters
Goodrive35
Function
Name
code
-decreasin
running. If it exceeds the level continuously, the
g ratio
output frequency will keep on decreasing to the
during
lower limit. If the output current is detected to be
current
lower than the limit level, the inverter will accelerate
limit
to run.
Setting range of P11.06:50.0~200.0%
Setting range of P11.07:0.00~50.00Hz/s
Overload
The output current of the inverter or the motor is
pre-alarm
above P11.09 and the lasting time is beyond P11.10,
P11.08
of
overload pre-alarm will be output.
motor/inver
ter
Overload
P11.09
pre-alarm
detection
Setting range of P11.08:
Enable and define the overload pre-alarm of the
Overload
inverter or the motor.
pre-alarm
P11.10
Setting range: 0x000~0x131
detection
LED ones:
time
0:Overload pre-alarm of the motor, relative to the
rated current of the motor
1:Overload pre-alarm of the inverter, relative to the
Detailed instruction of parameters
133
www.barghmaher.ir
Function codes
Default
Modify
value
Hz/s
0x000
150%
1.0s