inverters
Goodrive35
Function
Name
code
frequency.
Setting range: 0.0~50.0s
The
The inverter will carry out DC braking at the braking
braking
current set before starting and it will speed up after
P01.03
current
the DC braking time. If the DC braking time is set to
before
0, the DC braking is invalid.
starting
The stronger the braking current, the bigger the
braking power. The DC braking current before
The
starting means the percentage of the rated current of
braking
the inverter.
P01.04
time before
The setting range of P01.03: 0.0~100.0%
starting
The setting range of P01.04: 0.0~30.0s
The changing mode of the frequency during start-up
and running.
0:Linear type
The output frequency increases or decreases
linearly.
ACC/DEC
P01.05
selection
1: S curve
P01.06
ACC time 0.0~50.0s
Detailed instruction of parameters
64
www.barghmaher.ir
Function codes
Default
Modify
value
0.0%
0.0s
0
0.1s