Function
Name
code
enabled 0: Enabled
1: Disabled
Ones: Enabling
0:Disabled
1:Enabled
Tens: Voltage selection
Stopping
0: Internal setting
P08.26
protection
1:P8.27 setting
After the valid undervoltage stopping, the inverter
will decelerate to stop according to the time set by
P08.05.
Stopping
P08.27
Setting range: 250.0~1000.0V
voltage
Fault reset
Fault reset times: set the automatic fault reset times.
P08.28
times
If the reset time exceeds this set value, the inverter
will stop to wait maintenance.
Interval time of automatic fault reset: the interval
Interval
time of
between the time when the fault occurs and the time
P08.29
automatic
when the reset action occurs.
Setting range of P08.28:0~10
fault reset
Setting range of P08.29:0.1~3200.0s
Frequency
The output frequency of the inverter changes as the
decreasing
load. And it is mainly used to balance the power
P08.30
ratio of the
when several inverters drive one load.
dropping
Setting range:0.00~50.00Hz
control
Goodrive35 supports the shift between two motors.
Motor
This function is used to select the shifting channel.
P08.31
shifting
LED ones: shifting channel
0: terminal shifting; digital terminal is 35
Detailed instruction of parameters
115
www.barghmaher.ir
Function codes
Default
Modify
value
0x00
450.0
V
0
1.0s
0.00
Hz
0