inverters
Goodrive35
The multi-function digital output terminals or multi-function relay output an ON signal when the set
PLC finishes a circle (or a stage).
P10.00 simle PLC
0
Stop after running one
time
1
Run at the final value
after running for one
time
2
Cycle
PLC method
Digital output 15
Simple PLC stage completion
Digital output 20
Simple PLC cycle completion
Relative parameters list:
Function
code
P10.00
P10.01
Simple PLC memory
P10.02
Multi-step speed 0
The running time of step
P10.03
P10.04
Multi-step speed 1
P10.05
The running time of step 1 0.0~6553.5s(min)
P10.06
Multi-step speed 2
P10.07
The running time of step 2 0.0~6553.5s(min)
P10.08
Multi-step speed 3
P10.09
The running time of step 3 0.0~6553.5s(min)
P10.10
Multi-step speed 4
P10.11
The running time of step 4 0.0~6553.5s(min)
P10.12
Multi-step speed 5
P10.13
The running time of step 5 0.0~6553.5s(min)
P10.14
Multi-step speed 6
P10.01 simple PLC memory seleciton
Power off during running
Running parameter
setting in all stages in
PLC
Normal running
200ms
Name
0:Stop after running once
1:Run at the final value after running
Simple PLC
once
2:Cycle running
0:Power loss without memory
1:Power loss memory
-100.0~100.0%
0.0~6553.5s(min)
0
-100.0~100.0%
-100.0~100.0%
-100.0~100.0%
-100.0~100.0%
-100.0~100.0%
-100.0~100.0%
www.barghmaher.ir
0
Power off without
memory
1
Power off with
0
memory
0
1
1
P10.36
Terminal function 23
PLC starting selection
Simple PLC stop reset
Detailed instruction of parameters
227
Basic operation instruction
Set frequency
Restart from the first
stage
P17.00
Restart form the frequency
of the pause stage
200ms
Default
value
0
0
0.0%
0.0s
0.0%
0.0s
0.0%
0.0s
0.0%
0.0s
0.0%
0.0s
0.0%
0.0s
0.0%