inverters
Goodrive35
8.6.2 Motor vibration
No
If set right V/F vibration
parameter or not
Set right parameter
8.6.3 Overvoltage
Yes
Check the load and
adjust
Motor vibration or
abnormal noise
Check the motor parameter
or motor type is right or not
Perform parameter
autotune or not
No
It id vector control or not
Yes
Check the speed loop and
current is right or not
Check if there is abnormal
vibration to the given
Check if there is abnormal
If the inverter fault, please
contact with our comapany
OV fault
No
Check if the voltage range is in
the standard one or not ?
Y
es
Check If UVW is short circuited to
Yes
to the earth and the configuration of
the output side is right or not?
Yes
Yes
Check if the ACC/DEC
time is too short
No
Check if the load
motor is in abnormal
reverse running
No
If the it is the inverter
fault, please contact with
our company
254
www.barghmaher.ir
Please set right
No
motor type and
parameters
Yes
No
Perform right
parameter autotune
Yes
Yes
No
Set right parameter
Yes
Yes
Check the given
frequency
No
Yes
Check the load
to the load
No
Ensure the power supply
meets the need
Settle the short circuit
and confabulate rightly
Yes
Check if shortening the
ACC/DEC time is allowed
No
Check if it
Yes
needs to use
the options
No
Adjust the braking
options and the resistor
Fault tracking
frequency
Shortening the
ACC/DEC time
Add braking optionds