temperature and the impact to the output capacity.
The inverter needs to derate on high carrier
frequency. At the same time, the leakage and
electrical magnetic interference will increase.
Applying low carrier frequency is contrary to the
above, too low carrier frequency will cause unstable
running, torque decreasing and surge.
The manufacturer has set a reasonable carrier
frequency when the inverter is in factory. In general,
users do not need to change the parameter.
When the frequency used exceeds the default
carrier frequency, the inverter needs to derate 10%
for each additional 1k carrier frequency.
Setting range: 1.2~15.0kHz
0:No operation
1:Rotation autotuning
Comprehensive motor parameter autotune
It is recommended to use rotation autotuning when
high control accuracy is needed.
Motor
2: Static autotuning 1(autotune totally); It is suitable
P00.15
parameter
in the cases when the motor can not de-couple from
autotuning
the load. The antotuning for the motor parameter will
impact the control accuracy.
3: Static autotuning 2(autotune part parameters);
when the current motor is motor 1, autotune P02.06,
P02.07, P02.08; and when the current motor is
motor 2, autotune P12.06, P12.07, P12.08.
0:Invalid
AVR
1:Valid during the whole procedure
P00.16
function
The auto-adjusting function of the inverter can
selection
cancel the impact on the output voltage of the
inverter because of the bus voltage fluctuation.
P00.17
Reserved Reserved
Detailed instruction of parameters
62
www.barghmaher.ir
Function codes
Default
Modify
value
0
1
0