Goodrive35
Function
Name
code
running stage, and set P10 to select the current
running frequency.
The multi-step speed has the priority when P00.06 or
P00.07 does not equal to 6, but the setting stage can
only be the 1~15 stage. The setting stage is 0~15 if
P00.06 or P00.07 equals to 6.
7: PID control setting
The running mode of the inverter is process PID
control when P00.06=7 or P00.07=7. It is necessary
to set P09. The running frequency of the inverter is
the value after PID effect. See P09 for the detailed
information of the given source, given value,
feedback source of PID.
8:MODBUS communication setting
The frequency is set by MODBUS communication.
See P14 for detailed information.
9:PROFIBUS/CANopen communication setting
The frequency is set by PROFIBUS/ CANopen
communication. See P15 for the detailed
information.
10:Ethernet communication setting(reserved)
See P16 for the detailed information.
11:Reserved
12:Pulse string AB setting
0:Maximum output frequency, 100% of B frequency
setting corresponds to the maximum output
B
frequency
frequency
P00.08
1: A frequency command, 100% of B frequency
command
setting corresponds to the maximum output
reference
frequency. Select this setting if it needs to adjust on
the base of A frequency command
Combinati
0: A, the current frequency setting is A frequency
P00.09
on of the
command
setting
1: B, the current frequency setting is B frequency
Detailed instruction of parameters
59
www.barghmaher.ir
Function codes
Default
Modify
value
○
0
○
0