inverters
Goodrive35
Function
Name
code
compensation)
Times of motor overload M = Iout/(In*K)
In is the rated current of the motor, Iout is the output
current of the inverter and K is the motor protection
coefficient.
So, the bigger the value of K is, the smaller the value
of M is. When M =116%, the fault will be reported
after 1 hour, when M =200%, the fault will be
Motor 2
reported after 1 minute, when M>=400%, the fault
overload
P12.27
will be reported instantly.
protection
coefficient
Setting range: 20.0%~120.0%
Correction
Correct the power displaying of motor 2.
coefficient
Only impact the displaying value other than the
P12.28
of motor 2
control performance of the inverter.
power
Setting range: 0.00~3.00
0: Display according to the motor type: only the
parameters relative to the current motor type are
Parameter
displayed for the convenient for the customers in this
P12.29
display of
mode.
motor 2
1: All parameters are displayed: all parameters are
displayed in this mode.
P13 Group
Synchronous motor control
Reduction
P13.00
0.0~100.0%
coefficient
of source
Detailed instruction of parameters
141
www.barghmaher.ir
Function codes
Default
Modify
value
100.0
○
%
●
●
0
◎
80.0%