inverters
Goodrive35
Running time
END
arrival
Keypad
PCE
communicatio
n fault
Parameters
UPE
uploading
fault
Parameters
DNE
downloading
fault
Electronic
LL
underload
fault
The actual running time of
the inverter is above the
internal setting running time.
The connection of the
keypad wires is not good or
broken.
The keypad wire is too long
and affected by strong
interference.
There is circuit fault on the
communication of the
keypad and main board.
The connection of the
keypad wires is not good or
broken.
The keypad wire is too long
and affected by strong
interference.
Communication fault.
The connection of the
keypad wires is not good or
broken.
The keypad wire is too long
and affected by strong
interference.
There is mistake on the data
storage of the keypad.
The inverter will report the
underload pre-alarm
according to the set value.
252
www.barghmaher.ir
Fault tracking
Ask for the supplier and adjust
the setting running time.
Check the keypad wires and
ensure whether there is mistake.
Check the environment and
avoid the interference source.
Change the hardware and ask
for service.
Check the keypad wires and
ensure whether there is mistake.
Change the hardware and ask
for service.
Change the hardware and ask
for service.
Check the keypad wires and
ensure whether there is mistake.
Change the hardware and ask
for service.
Repack-up the data in the
keypad.
Check the load and the
underload pre-alarm point.