Siemens SINUMERIK Commissioning Manual page 674

Sinumerik 840di sl/840d sl/840dbase software and hmi advanced
Hide thumbs Also See for SINUMERIK:
Table of Contents

Advertisement

Configuring the system
2.1 System settings
2.1.2
How to set the IP address of the PCU 50.3
Default
NOTICE
The IP address 192.168.214.241 is set as a factory default for every PCU 50.3 on the
system network.
You must only perform the steps described below if you wish to change this default.
Procedure
1. Select the following on the PCU on the service desktop: "Start" → "Settings" → "Network
2. Double-click the Ethernet 2 interface you want to parameterize which is to be used for
3. Under the "General" tab, select "Internet Protocol (TCP/IP)" and click the "Properties"
34
Connections".
The "Network Connections" window opens.
connecting the TCU or system network.
The "Ethernet 2 (System Network) Properties" window opens.
button.
The "Internet Protocol (TCP/IP) Properties" window opens:
Commissioning Manual, 03/2009, 6FC5397-1DP10-4BA0
PCU-Basesoftware (IM8)