Diagnostics and service
5.6 Action log
5.6
Action log
5.6.1
Setting the action log
Overview
The "action log" function can be used to log operating sequences. By default, if the action log
is enabled, the data that can be logged are recorded. The action log setting is password-
protected (access level 3: end user).
Using the operating area "Start-up" → "HMI" → "System Settings," select which actions of the
control should be logged in the "Action log settings":
Figure 5-7
Logging on/off
Additional settings:
• The path of the log file is permanently set and cannot be changed.
• File size of log file:
• Transmission Write interval:
• Program status when an
152
Action log settings
alarm occurs:
in bytes
− 1: The log is only saved to hard disk upon request,
e.g. trigger, (default setting).
> 0: The longest waiting time in seconds before a log file
is saved on hard disk.
Alarm number entry separated by a comma: The alarms
entered here are immediate triggers for immediately
saving the current action log on the hard disk.
Commissioning Manual, 03/2009, 6FC5397-0DP10-3BA0
HMI Advanced (IM4)