DIAGNOSIS USING THE MANIFOLD GAUGE
On normal operation during the cooling cycle, the
manifold gauge must indicate approximately 1.5 - 2.0
kg/cm
2
at low pressure side and 14.5 - 15 kg/cm
high pressure side, on condition that the temperature
at the cooler inlet, 30 º C - 35 º C, 2,000 rpm of the
engine rpm , full cold and maximum blower speed.
Symptom
1. High and low pressure are abnormally low.
2. Air at cooler outlet is not cold.
1. High and low pressure are abnormally high.
1. High and low pressure are abnormally high.
2. Connection at the low pressure is not cold.
SSANGYONG Y200
2
at
Cause
•
There is a gas leak in the
cooling system.
YAD7B080
•
Insufficient cooling and
faulty condenser cooling
by excessive
refrigerant.
YAD7B090
•
Belt is slipped
•
There is an air in the
cooling system
YAD7B100
GENERAL HVAC SYSTEM 7B-11
Action
•
Check the oil leak,
repair
•
Add the refrigerant
•
Keep the specified
amount of the
refrigerant, Clean the
condenser
•
Repair the belt
•
Clean and repair the
receiver-drier
•
Check the oil
contamination etc.