Product description of safety module CAMC-G-S3
2.10.2
Status display on the safety module
To display the status of the safety function, the safety module has an LED on its front side è Section 5.4.1.
The status LED displays the operating status of the safety module. The display is exclusively for dia
gnostics and must not be used in a safety-orientated way.
If multiple statuses are pending simultaneously which result in a display, then the status with the
highest priority is displayed. The priorities are shown in Tab. 2.88.
The display is a continuous light or flashes at approx. 3 Hz.
LED indicator
Status signal
Flashes red
VOUT_ERROR = 1
g
c
g
c
g
Lights up red
VOUT_SCV = 1
g g g g g
VOUT_SFR = 1
Lights up yel
VOUT_SSR = 1
low
VOUT_SFR = 1
g g g g g
Flashes yellow VOUT_SFR = 1
c
g
c
g
c
Flashes red/
VOUT_SERVICE = 1
green
VOUT_PS_EN = 1
g
g
g
g
g
Flashes green
VOUT_SERVICE = 1
g
c
g
c
g
VOUT_PS_EN = 0
Illuminates
VOUT_READY = 1
green
VOUT_PS_EN = 1
g g g g g
Off
VOUT_READY = 0
c c c c c
VOUT_PS_EN = 0
Tab. 2.88
System statuses and messages
134
Prio
Status, safety module
7
"System Error"
6
"Safety Condition Viol
ated", error response
initiated
5
"Safe State Reached",
safe status achieved
4
"Safety Function Re
quested"
3
"Delivery Status"
2
"Service" status
1
"Ready", operational
0
"Initialisation Running" Initialisation 1: Load para
Festo – GDCP-CAMC-G-S3-EN – 1406NH – English
Internal status
The entire system is in the
"System Error" or "Commu
nication Error" status.
Violation of at least one of
the currently required safety
functions.
All requested safety func
tions are in the status "Safe
State Reached".
The signal is active as soon
as at least one safety func
tion is requested.
It remains active until all the
requests have been reset.
The delivery status can be
distinguished from the "Ser
vice status" using
VOUT_PS_EN.
No parameters present, para
meter invalid or paramet
erisation session is running.
Operational, no safety func
tion requested, no errors.
meter, Initialisation 2: Estab
lish communication.