Technical appendix
Sensor type
13: Terminate safety
function (restart)
1) To EN ISO 13849-1
2) To EN 61800-5-2
Tab. A.17 Safety reference data for digital inputs
Please note
– The following data on measures and DC is based on the data of the standard EN ISO
13849-1.
– The manufacturer's specifications must be used for a safety-related assessment of
the sensors.
– The DC values given are only valid when the specified measures and the specified
additional conditions are complied with.
– Fault exclusions are possible according to the relevant standards, for which the
required conditions must be permanently guaranteed.
Measure
Cyclical test pulse created by dynamically
changing the input signals.
Cross-comparison of input signals with dy
namic test if short-circuits cannot be de
tected (for multiple inputs/outputs).
Cross-comparison of input signals with im
mediate and intermediate results in the
logic (L) and temporal as well as logic pro
gram sequence monitoring and detection
of static failures and short circuits (for
multiple inputs/outputs).
Plausibility check, e.g. use of normally
open and normally closed contacts.
Tab. A.18 Measures for digital inputs
240
Switch type
1 N/O contact
DC
90
90
99
99
Classification category, PL
Without allocation of test
pulse Cat. 1, PL c
With allocation of test pulse
Cat. 2, PL d
Comment
Only effective when alloca
tion of test pulses is active.
Without allocation of test
pulses.
Cyclical change of the input
signals required, e.g.
through the process or regu
lar actuation.
Only with allocation of test
pulses.
Only when using antivalent
signals.
Festo – GDCP-CAMC-G-S3-EN – 1406NH – English
1)
Classification
2)
SIL
SIL 1
SIL 2
Use
Cross-circuit mon
itoring for 1-chan
nel sensors.
Monitoring of
2-channel
sensors.
Monitoring of
2-channel
sensors.
Monitoring of
2-channel
sensors.