Safety module
Table of Contents

Advertisement

2
Product description of safety module CAMC-G-S3
Term/abbreviation
Safety Function Request SFR
Safe State Reached SSR
n
act
Tab. 2.49 Legend for Fig. 2.23
If parameterised appropriately with "Activate quick stop ramp in basic unit" (P0B.02), the motor con­
troller is instructed via the "Quick stop" cable to stop the drive.
After the time "Time delay until monitoring starts" (P0B.00) has elapsed, the drive is monitored to
check it is idling. At this time, the output "Safe state reached" becomes active if the safety condition is
not violated.
Whilst the time P0B.00 elapses, position monitoring is not yet active. After P0B.00 has elapsed, the
current position is saved and is used as the setpoint for the position to be monitored. The position is
monitored by comparing the current position value at regular intervals with the saved value.
After the request of the safety function SOS, the following times elapse until the safety function is ac­
tivated and errors are detected:
Time delays from VIN_SOS_RSF
VOUT_SOS_SFR
VOUT_SOS_SSR
Detection of a violation of the safety condi­
1)
tion
after P0B.00 within
1) The safety condition is considered as violated when...
a) The monitoring window is exited +/- P0B.01 or
b) An axle movement is detected via idling detection within the position window
Tab. 2.50 SOS time delays
Parameters for SOS
SOS: Safe Operating Stop
No.
Name
P0B.00
Time delay until monitoring starts
P0B.01
Tolerance window, position monitoring
P0B.03
Automatic restart permitted
Expert parameter
P0B.02
Activate quick stop ramp in the basic
unit
Tab. 2.51 SOS: Safe Operating Stop
94
Explanation
Safety function request
Safe state reached
Actual speed
Minimum
2.0 ms
2.0 ms + P0B.00 2.1 ms + P0B.00 2.0 ms + P0B.00
0.0 ms
Description
Time delay after request of the function up to the
start of monitoring
Limit value for movement after idle status is
reached
If set: Cancellation of the request (restart) if an
inactive request arrives
Send brake command to the basic unit (Signal
SS1) Yes / No
Festo – GDCP-CAMC-G-S3-EN – 1406NH – English
Maximum
Typical
2.1 ms
2.0 ms
2.0 ms
2.1 ms