Input/output data
Data format of input word "Sign + 15 bits, right-justified"
D15
D14 D13 D12 D11 D10 D9
VZ
B14 B13 B12 B11 B10 B9
MSB
Abbreviations used
VZ
Sign
B0
B14
Pressure change value
...
DO
D15
16-bit input data field
...
MSB/LSB
Most significant bit /least significant bit
Tab. 22 Data format of input word Em.5/Em.6 "Pressure change"
8.2.8
Input word Em.3 "Module status" [Status]
In the input word Em.3, status information on the module is displayed.
Data format of input word "16 bits, right-justified"
D15
D14 D13 D12 D11 D10 D9
B15
B14 B13 B12 B11 B10 B9
MSB
Abbreviations used
B0
Status of shut-off valve
B1
Monitoring sensor supply
B2
Status of electrical input 0
B3
Status of electrical input 1
B4, B5
Status Q_low-Timer
B6
Monitoring of lower critical limit pressure P2
B7
Measurement of impulse consumption VC
B8
B11
Module status
...
B12
Status of consumption V0
B13
Status of consumption V1
B14
Monitoring of electrical output 0
B15
Monitoring of electrical output 1
D0
D15
16 bit input data field
...
MSB/LSB
Most significant bit /least significant bit
Tab. 23 Data format of the input word Em.3 "Module status"
Festo — MSE6-C2M — 2019-03
D8
D7
D6
D5
B8
B7
B6
B5
D8
D7
D6
D5
B8
B7
B6
B5
D4
D3
D2
D1
B4
B3
B2
B1
D4
D3
D2
D1
B4
B3
B2
B1
D0
B0
LSB
D0
B0
LSB
47